Horne Engineering Ltd
Issue 3 8/05 7
6.6.3 Insert the ADJUSTING SCREW (2) into the VALVE COVER (3) and turn anti-
clockwise until the top of the ADJUSTING SCREW (2) is approximately 5mm
below the top of the lockshield.
6.6.4 When the internal components have been located loosely in the valve body, place
the VALVE COVER (3) over the THERMOSTAT ELEMENT ASSEMBLY (6)
and then push gently and turn until the thread on the VALVE COVER (3) engages
with the VALVE BODY (10). The internal components are self-aligning.
6.7 Check Valves
6.7.1
Check Valves are located within the STRAINER COUPLING (11). They are not
removable. They are designed for a long, maintenance-free life.