Introduction: 

 
The HE500232485 is a compact, lightweight and reliable RS232 to RS485 converter, which provides 
RS485 half-duplex (2-wire) multi-drop functionality to OCS devices that only support RS232 
communications (Mini, OCS100, OCS200).  The HE500232485 may also be used to provide RS232 to 
RS485 conversion for other devices provided they assert RTS handshaking when RS485 transmission is 
required and that handshake line is connected to the converter’s RS232 CTS line. 
 
RS-232 is a point-to-point serial communications standard that defines the electrical and mechanical 
details of the interface between Data Terminal Equipment (DTE) and Data Communications Equipment 
(DCE). Compared with newer standards RS-232 is limited in terms of data rate, maximum distance and 
noise immunity.  For longer distances, higher speeds, more noise immunity and the need for multi-drop 
connections, conversion to RS-485 is recommended. 
 

Connections: 

 

    < 

put 

diagram 

 

here> 

 
 
 
 
 

RS232 - 

direct or through a RS232 cable to a DCE DB9 connector. 

RS485 - 

connect the RS485 data lines to the D+ and D- terminals (observing polarity).  Note 
that the communications common may be connected to the 0V terminal; however, 
since converter is not isolated, standard practices should be applied to avoid ground 
loops. 

Power - 

connect 12-24VDC (100mA max) to the V+ and 0V terminals (observing polarity). 

Termination –

 when the pin jumper is installed (board side opposite terminal connections), 

internal termination resistance (120ohm) is provided. 

 

Cables:  
 

The HE500232485’s RS232 connection (DB-9P) is a wired as a DTE configuration, which allows for direct 
connection to OCS device’s RS232 programming/communication ports.  If cabling is required between 
the HE500232485 and an OCS, it must be straight through and pass the CTS handshake signal as well 
as the data lines. 
 
When connecting the HE500232485 to another DTE device (such as a PC) a ‘null modem’ or crossover 
cable is required (which must also pass the DTE device’s RTS handshake output to the HE500232485’s 
CTS handshake input) 
 
The RS-232 standard suggests operation is possible at about 20 kbps over distances of 50 feet, 
depending on grounding and noise considerations.  Over short distances, RS-232 is sometimes operated 
at rates as high as 115.2 kbps. Several hundred feet is possible at data rates of 9600 bps or lower.  

OCS RS-232 to RS485 Serial 

Adapter

 

HE500232485 

Summary of Contents for HE500232485

Page 1: ...RS232 cable to a DCE DB9 connector RS485 connect the RS485 data lines to the D and D terminals observing polarity Note that the communications common may be connected to the 0V terminal however since converter is not isolated standard practices should be applied to avoid ground loops Power connect 12 24VDC 100mA max to the V and 0V terminals observing polarity Termination when the pin jumper is in...

Page 2: ... extended using a variety of repeater products on the market Data is transmitted differentially on two wires twisted together referred to as a twisted pair CSCAPE configuration To enable an OCS device for use with the HE500232485 converter an Open function block must be provided that configures the associated OCS port for Multidrop Half handshaking This configuration allows the OCS to drive the HE...

Page 3: ...he prior agreement and written permission of Horner APG Inc Information in this document is subject to change without notice HE500RS232485 4 Pin I O Header Pin configuration RS 485 half duplex Pin RS 485 Function 0V 0VDC Supply V 12 to 24VDC Supply 100mA Max D RS 485 Data D RS 485 Data ...

Page 4: ...ke sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace immediately if defective TECHNICAL SUPPORT For assistance and manual updates contact Technical Support at the following locations North America Europe 317 916 4274 353 21 4321 266 www heapg com www horner apg com techsppt heapg com techsupport hornerirl ...

Reviews: