DESCRIPTION 

 
The Horner APG High Density Thermocouple Input Module offers superior channel density, with 16 input 
channels per module.  This module allows thermocouple temperature sensors to be directly connected to 
the PLC without external signal processing (transducers, transmitters, etc.).  All analog and digital 
processing of the thermocouple signal is performed on the module.  Temperature resolution is 0.5°C, and 
temperature values may be reported to the PLC %AI I/O table in 0.5°C or 0.5°F increments.  This module 
features open circuit detection, where the %AI register goes to its maximum value upon an open circuit 
condition, and a corresponding %I bit is energized.  Field wiring is connected to a special high density, 32 
position removable terminal block.  

Recommended wire size is 24 AWG.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 1 – HE693THM166 (Front View)               Figure 2 – HE693THM166 (Right Side View)

 

 
 
 
 
 

 
06 December 2004 

 

 

 

 

 

 

 

 

MAN0090-05 

 
 

High Density

Thermocouple Input

Module

Product Specifications

and Installation Data

 

16 CHANNEL 

 THERMOCUPLE

 

 

HE693THM166 S/N: 1965 

Horner APG, LLC. 

Summary of Contents for HE693THM166

Page 1: ... temperature values may be reported to the PLC AI I O table in 0 5 C or 0 5 F increments This module features open circuit detection where the AI register goes to its maximum value upon an open circuit condition and a corresponding I bit is energized Field wiring is connected to a special high density 32 position removable terminal block Recommended wire size is 24 AWG Figure 1 HE693THM166 Front V...

Page 2: ...ode Rejection 100dB A D Conversion Type Integrating Input Range Temp X 210 to 1200 C 2 C Maximum Reading not guaranteed below 200 C N 270 to 1300 C R 0 to 1768 C C 0 to 2320 C A D Conversion Time 40 channels per second Resolution 0 5 C or 0 5 F Operating Temperature 0 to 60 C 32 to 140 F Accuracy 0 5 C typical J K N T Relative Humidity 5 to 95 non condensing NOTE Model F and later support the Exte...

Page 3: ...ets the thermocouple type The effect of digital filtering set with Byte 2 on module response to a temperature change temp change completed vs time Table 3 Temperature Scaling Byte 3 Formula 0 C AI 2 1 F AI 2 Temperature values are written to the AI registers in 0 5 C or 0 5 F increments depending upon the value of Byte 3 0 10 20 30 40 50 60 70 80 90 100 0 2000 4000 6000 8000 Temperature Change Com...

Page 4: ... twisted pair extension wiring offers best noise immunity If shielded wiring is used a good earth ground connection is critical Recommended wire size for terminal strip is 24 AWG Adhere to the following safety precautions whenever any type of connection is made to the module Connect the green safety earth ground first before making any other connections When connecting to electric circuits or puls...

Page 5: ...aking any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace immediately if defective 6 TECHNICAL ASSISTANCE For manual updates and assistance contact Technical Support at the following locations North Ame...

Page 6: ...PAGE 6 06 December 2004 MAN0090 05 NOTES ...

Reviews: