background image

Instruction Manual 

Microprocessor Temperature Regulator HT MC11

Page 17 of 22

Autotune:

The tuning algorithm determines characteristic values within the controlled process
and calculates valid feedback parameters (P, D, I) and cycle time (= 0.3 x D) for a PD/I-
controller.
The autotune mode is activated during start-up shortly before the setpoint is reached.
If autotune is activated after the setpoint has already been reached, the temperature
will first fall approx. 5 % below the measuring range in order to determine optimal
control system parameters.
Autotune can be initiated any time by setting 

 OPt

 = 

 on

.

After finishing calculation of feedback parameters, the controller leads the process
value to the setpoint value.
Autotune can be stopped by setting 

 OPt

 = 

 OFF

.

During autotune the display shows 

 OPt

 alternating with the setpoint value.

Preconditions for starting the autotune algorithm:

Setpoint value must be higher than 5 % of measuring range

Sensor must not have a failure

Softstart function must not be active

 OPt

autotune

 OFF

 autotune not active

 on

   autotune active (one time)

Auto

Autotune starts each time the controller is turned on if
the   difference   between   setpoint   and   actual   process
value is more than 7 % of the measuring range.

OFSt

 

process value Offset

-999 …  

 OFF

 …  1000

Parameter for correction of input signal:

correction of a gradient between measuring point and sensor 
tip

line resistance balancing of 2-line RTD (Pt100) sensors

correction of control deviation when using P or PD action

Example: if the offset value is set to +5 °C, the real temperature
measured by the sensor (when process is balanced) is 5 °C less
than the setpoint and the displayed actual process value.
Ensure that the corrected temperature process value is within
the selected measuring range.

Version 1080/1.03 02/2018

471 11 400

Horst GmbH
Bitzenheimer Weg 10
D-64653 Lorsch
Telefon:  +49 (0) 6251 9626 0
Telefax: +49 (0) 6251 9626 96

Summary of Contents for HT MC11

Page 1: ...Output 0 10 V DC Option 8 6 4 Setpoint Adjustment 0 10 V DC Option 8 6 5 Potential Free Switching 8 7 Before First Operation 8 8 Parameter Description 9 8 1 Device Configuration Level 9 8 2 Alarm Conf...

Page 2: ...06 20 65 HT MC11 15 A KV Nominal current max 15 A Connection via cable glands Switching power at 230 V AC 3450 W 06 20 66 HT MC11 15 A plug socket 2 sensors Nominal current max 15 A Switching power a...

Page 3: ...re is required according to DIN EN 60519 2 DIN VDE 0721 part 2 Safety in electroheat installations Part 2 Particular requirements for resistance heating equipment 1 Description Due to high configurabi...

Page 4: ...In program controller mode keys are used for program functions instead of setpoint selection key E Confirmation and storage of the preselected values The display briefly shows a light chain for confi...

Page 5: ...tion level can be entered by pressing keys P and E for approx 1 second by pressing keys P and E longer the device configuration level can be reached Selection and adjustment of parameters as described...

Page 6: ...nly connect ohmic consumers to the regulator Permissible ambient temperature 0 40 C must be observed even in unfavor able circumstances Avoid direct sunlight Ensure sufficient ventilation The regulato...

Page 7: ...is switched off if the temperature exceeds the limit value The limit value is adjusted with parameter AL L see page 10 The supervision function must be activated by the parameter rEL C It is possible...

Page 8: ...range value max measuring range value of the selected control sensor 2 The analog output works in output ratio mode The output ratio is used e g for thyristor control see page 9 Out H Connection via c...

Page 9: ...752 F L8 C Thermocouple TC Fe CuNi L 0 800 C L8 F Thermocouple TC Fe CuNi L 32 1472 F J8 C Thermocouple TC Fe CuNi J 0 800 C J8 C Thermocouple TC Fe CuNi J 32 1472 F k1 C Thermocouple TC NiCr Ni K 0 8...

Page 10: ...lected switching cycle time is divided by 4 for slower and more uniform heating up Once the process value reaches the softstart setpoint the temperature is kept con stant for a preselectable duration...

Page 11: ...changed to manual mode using the last valid output ratio Manual mode is indicated with a leading H in the setpoint display followed by the output ratio The output ratio can be changed manually In foll...

Page 12: ...nt 2 is active Pr St Close ext contact start program controller Open ext contact stops program controller CL SH Close ext contact release self hold of temperature monitoring CLear Self Hold L0C Adjust...

Page 13: ...larm AL1 Temperature must be lower to activate alarm Over temperature alarm is not active AL1 OFF Both sided alarm limit alarm Temperature must be outside the selected range to activate alarm Both ala...

Page 14: ...lay time Alarm 1 OFF 1 1000 s rF A2 Alarm 1 configuration reference Alarm 2 AbS absolute bASE based on setpoint Cur Heating current monitoring works like absolute alarm rE A2 Relay action for alarm 2...

Page 15: ...tio limitation value Warning Output ratio limitation does not work during auto tune C Ly Max output ratio limitation cooling PID 0 100 See output ratio limitation heating Adjustment of Control Paramet...

Page 16: ...0 s optimal value for fast control loops 0 8 s Relay outputs cycle time 15 s The adjusted cycle time should be as long as possible to mini mize the wear of the relay contacts C P prop band P cooling P...

Page 17: ...starting the autotune algorithm Setpoint value must be higher than 5 of measuring range Sensor must not have a failure Softstart function must not be active OPt autotune OFF autotune not active on au...

Page 18: ...te OFF SP Lo SP Hi 500 Alarm active if actual process value is higher than alarm value rF A1 bASE based on setpoint OFF 1 100 K Alarm active if actual process value is higher than setpoint alarm value...

Page 19: ...hes Pressing again key sets program on hold Display shows hoLd for a short time ramp LED is on Resume program by pressing key again Display shows rESu ramp LED flashes Stop program by pressing key Dis...

Page 20: ...ion by setting value to 0 min I SP Step 1 Ramp setpoint SP Lo SP Hi Setpoint for this step I ti Step 1 Dwell time 0 6000 min The dwell time starts after the ramp has finished The con troller works usi...

Page 21: ...If error message continues please send the controller back to the manufacturer Err 9 Internal Error Communication error Send the controller back to the manufacturer Er Cn Reference junction temperatur...

Page 22: ...er 1 1000 If the range is exceeded the controller may be damaged Logic output Bist voltage signal 0 9 5 V DC max 10 mA short circuit proof Output relay AL1 Relay max 250 VAC max 2 A ohmic load Output...

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Reviews: