Instruction Manual
Microprocessor Temperature Regulator HT MC11
Page 18 of 22
8.4 Operating Level
The controller shows the process and the setpoint value if none of the following pa-
rameters are selected.
t.L i
temperature limit
Display of temperature of the supervision unit
Cur
actual heating current value
Display of actual heating current value. By pressing key
the leakage current is displayed.
SP2
setpoint
2
OFF
,
SP.Lo
SP.Hi
Function and configuration of alarms are described in chapter alarm configuration level .
On operating level only alarm values can be set.
Alarm reference
Adjustment range
AL 1. %
Alarm 1:
alarm value
under-temperature or current
underrun
rF.A1
=
AbS
absolute
OFF
,
SP.Lo
SP.Hi
Alarm active if actual process value is
lower than alarm value
rF.A1
=
bASE
based on setpoint
OFF
, -1 -100 K
Alarm active if actual process value is
lower than (se alarm value)
AL 1. #
Alarm 1:
alarm value
over-temperature or current
overrun
rF.A1
=
AbS
absolute
OFF
,
SP.Lo
SP.Hi
< 500>
Alarm active if actual process value is
higher than alarm value
rF.A1
=
bASE
based on setpoint
OFF
, 1 100 K
Alarm active if actual process value is
higher than (se alarm value)
AL 2. %
Alarm 2:
alarm value
under-temperature or current
underrun
rF.A2
=
AbS
absolute
OFF
,
SP.Lo
SP.Hi
Alarm active if actual process value is
lower than alarm value
rF.A2
=
bASE
based on setpoint
OFF
, -1 -100 K
Alarm active if actual process value is
lower than (se alarm value)
AL 2. #
Alarm 2:
alarm value
over-temperature or current
overrun
rF.A2
=
AbS
absolute
OFF
,
SP.Lo
SP.Hi
Alarm active if actual process value is
higher than alarm value
rF.A2
=
bASE
based on setpoint
OFF
, 1 100 K <30>
Alarm active if actual process value is
higher than (se alarm value)
ProG
Program controller
OFF
Program controller not activated
on
Program controller activated
cnt.S
and following param-
eters see program controller
Following parameters are not available if parameter
ProG
=
OFF
.
Version 1080/1.03 02/2018
471 10 1400
Horst GmbH
Bitzenheimer Weg 10
D-64653 Lorsch
Telefon: +49 (0) 6251 9626 0
Telefax: +49 (0) 6251 9626 96
only relevant for option
heating current monitoring