17
5) Defrost
A1. Temperature-Initiation
1)
Refrigerator–LED 5 (ConFM) is on. LED 3 (EvapFM on) is off
: DTh cools to
13°F (-10°C) (8°F (-13°C) for Pass-Thrus). 20 min. minimum off cycle defrost
starts. Cabinet temperature displayed on DB. EvapFM continues. ConFM
continues or energizes.
2)
RFH1-SSB(-HD)(-HS)(-HSE) Refrigerator–LED 5 (unused) is on.
LED 3 (EvapFM on) is off:
DTh cools to 13°F (-10°C). 20 min. minimum off
cycle defrost starts. Cabinet temperature displayed on DB. EvapFM continues.
Comp and ConFM de-energize.
A2. Time-Initiation
If the factory time-initiated setting is moved from 0 defrosts per 24 hours, the
appliance enters the defrost cycle when the time of the new setting terminates.
Defrost timer terminates, CB initiates defrost. Defrost sequence same as
"5)A1. Temperature-Initiation" above.
B. Defrost Termination
1)
Refrigerator–LEDs 4 (Comp) and 5 (ConFM) are on. LED 3 (EvapFM on) is
off
: DTh warms to 40
°
F (4
°
C). EvapFM and ConFM continue. 2.5 minute Comp
delay timer terminates. Comp energizes.
2)
RFH1-SSB(-HD)(-HS)(-HSE) Refrigerator–LEDs 4 (Comp and ConFM) and
5 (unused) are on. LED 3 (EvapFM on) is off:
DTh warms to 40
°
F (4
°
C).
EvapFM continues. 2.5 minute Comp delay timer terminates. Comp and ConFM
energize.
Note:
• Perimeter heater controlled by perimeter heater switch.
• Glass door (-GD models) heater controlled by glass door heater switch.
• CPM RFH1-SSB(-HS)(-HSE) Refrigerator: CPM has power supply as soon as the
power switch is placed in the "ON" position. CPM operates as needed via the float
switch.
Legend:
CB
–control board;
Comp
–compressor;
ConFM
–condenser fan motor;
CPM
–condensate pump motor (RFH1-SSB(-HS)(-HSE) Refrigerator);
CTh
–cabinet
thermistor;
DB
–display board;
DTh
–defrost thermistor;
EvapFM
–evaporator fan
motor;
F/S
–float switch