2. Sequence Flow Chart
a) Refrigerator
DTh cools to 13°F
(-10°C) (8°F (-13°C)
for Pass Thru) or
optional defrost timer
terminates
Legend:
Comp
-compressor
ConFM
-condenser fan motor
CTh
-cabinet thermistor
DTh-
defrost thermistor
EvapFM
-evaporator fan motor
2. Cool Down
3. Cool Down Achieved
Comp
energized
ConFM
energized
EvapFM
energized
CTh in control
CTh cools
to 3°F (1.7°C)
below setpoint
CTh w
ar
ms
to 3°F (1
.7°C)
abo
ve setpoint
5. Defrost
EvapFM
energized
Comp
de-energized
ConFM
de-energized
DTh warms to
40°F (4°C)
2.5-min.
Comp delay
timer starts
Note:
• 2.5-minute minimum compressor on and off time.
• Evaporator fan motor de-energizes when door is open.
• 20-minute minimum defrost time.
• Perimeter heater controlled by perimeter heater switch.
• Glass door (-GD models) heater controlled by glass door
heater switch.
• RFH1-SSB(-HS)(-HSE): Condensate pump motor has
power supply as soon as the power switch is placed in
the "ON" position. Condensate pump motor energizes as
needed via the float switch.
DTh in control
ConFM
energized
EvapFM
energized (except RFH1)
Comp
de-energized
EvapFM
energized
2.5-min. Comp on
timer starts
4. Cool Down Restart
2.5 min.
Comp Delay
"RI-A" Control Board
Refrigerator Sequence Flow Chart
2.5-min. Comp off
timer starts
1. Startup