PROBLEM CHECK POSSIBLE
CAUSE
REMEDY
3. Condenser water
pressure too low or OFF
(water-cooled).
3. Check for recommended
pressure.
1. Set too high.
1. Adjust lower.
b) Water Regulator
(water-cooled)
2. Clogged or defective.
2. Clean or replace.
1. Bad contacts.
1. Check for continuity and
replace.
2. Voltage too low.
2. Check for recommended
voltage.
c) Overload
Protector
3. Refrigerant overcharged
or undercharged.
3. Recharge.
d) Starter
1. Defective.
1. Replace.
e) Start Capacitor
or Run
Capacitor
1. Defective.
1. Replace.
1. Bad contacts.
1. Check for continuity and
replace.
f) Power Relay
(Magnetic
Contactor for
240ME/WME)
2. Coil winding opened.
2. Replace.
1. Wiring to Compressor.
1. Check for loose
connection or open, and
repair or replace.
g) Compressor
2. Defective.
2. Replace.
[2] (Continued)
h) Air Filter,
Condenser
1. Clogged.
1. Clean.
[3] Compressor
runs, but other
components
will not start.
a) Control Circuit
1. Loose connection or
broken wire.
1. Repair or replace.
a) Wiring
1. Loose connection or
broken wire.
1. Repair or replace.
b) Actuator Toggle
Switch
1. Defective.
1. Replace.
[4] Fan Motor will
not run.
c) Thermistor,
Controller Board
1. See “II. 2. CONTROLLER BOARD”.
a) Water Solenoid
Valve
1. Diaphragm does not
close.
1. Check for water leaks
with icemaker OFF.
[5] Water
continues to be
supplied in
freeze cycle.
b) Controller Board
1. Defective.
1. See “II. 2. CONTROLLER
BOARD”.
a) Water Supply
Line
1. Water pressure too low
and water level in Water
Tank too low.
1. Check for recommended
pressure.
b) Water Solenoid
Valve
1. Dirty mesh filter or orifice
and water level in Water
Tank too low.
1. Clean.
1. Water leaks.
1. Check connections for
water leaks, and repair.
c) Water System
2. Clogged.
2. Clean (See “V. 4.
ICEMAKING WATER
SYSTEM”).
1. Motor winding opened.
1. Replace.
[6] Water does not
circulate.
d) Pump Motor
2. Bearing worn out.
2. Replace.
92
Summary of Contents for IM-100
Page 5: ...1 I SPECIFICATIONS 1 DIMENSIONS CONNECTIONS a IM 25LE Air cooled ...
Page 6: ...2 b IM 25CLE Air cooled Until March 2000 production Auxiliary Code K 1 ...
Page 7: ...3 c IM 21CLE IM 25CLE IM 30CLE Air cooled From April 2000 production Auxiliary Code K 2 ...
Page 8: ...4 d IM 45LE Air cooled ...
Page 9: ...5 e IM 45CLE 25 Air cooled ...
Page 10: ...6 f IM 65LE Air cooled ...
Page 11: ...7 g IM 100LE IM 130LE IM 130ME Air cooled ...
Page 12: ...8 h IM 100CLE Air cooled ...
Page 13: ...9 i IM 160ME Air cooled ...
Page 14: ...10 j IM 240ME Air cooled ...
Page 15: ...11 k IM 240M2E Air cooled ...
Page 16: ...12 l IM 25WLE IM 30WLE Water cooled ...
Page 17: ...13 m IM 45WLE Water cooled ...
Page 18: ...14 n IM 65WLE Water cooled ...
Page 19: ...15 o IM 100WLE IM 130WLE IM 130WME Water cooled ...
Page 20: ...16 p IM 240WME Water cooled ...
Page 21: ...17 q IM 240WM2E Water cooled ...
Page 70: ...66 2 WIRING DIAGRAM a IM 21CLE IM 25LE IM 25CLE IM 30CLE IM 25WLE IM 30WLE ...
Page 71: ...67 b IM 25L IM 25CL IM 25WL ...
Page 72: ...68 c IM 45LE IM 45CLE 25 IM 45WLE ...
Page 73: ...69 d IM 65LE IM 65WLE ...
Page 74: ...70 e IM 65L IM 65WL ...
Page 76: ...72 g IM 130LE IM 130WLE Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Page 78: ...74 i IM 130ME IM 130WME Note The Washing Switch is provided only after the Auxiliary Code H 0 ...
Page 80: ...76 k IM 160ME ...
Page 81: ...77 l IM 240ME IM 240WME ...
Page 82: ...78 m IM 240M2E IM 240WM2E ...
Page 120: ...116 Fig 30 ...