29
Control Board (CB) Setting Menu
Category
No. Item
Range
IM-200BAC
Default
Water Tank
Ice Control
70
71
72
74
If control board thermistor temperature is above the water
tank ice control lower temperature setting (CB Setting 74)
and equal to or less than the water tank ice control upper
temperature setting (CB Setting 70) when freeze cycle
termination temperature (CB Setting 2) is met, the hot gas
valve energizes/de-energizes/energizes for the times set by
the hot gas valve energized/de-energized times
(CB Settings 71 and 72) to reduce bonding of the water
tank to the evaporator.
See Ranges Below See
Defaults
Below
Water Tank
Ice Control
& Ice Bridge
Control
70 Water Tank Ice Control Upper Temperature
See CB Setting 70, 71, 72, 74 description above.
Ice Bridge Control Temperature
See CB Setting 73 description below.
10 to 60°C
(1°C increments)
39
Water Tank
Ice Control
71 Water Tank Ice Control Hot Gas Valve Energized Time
See CB Setting 70, 71, 72, 74 description above.
0 to 20 sec.
(1 sec. increments)
10
72 Water Tank Ice Control Hot Gas Valve De-Energized Time
See CB Setting 70, 71, 72, 74 description above.
10 to 60 sec.
(1 sec. increments)
20
Ice Bridge
Control
73 Ice Bridge Control Hot Gas Valve De-Energized Time
Time hot gas valve is de-energized after 20 sec. in
harvest cycle if control board thermistor temperature is
above the ice bridge control temperature (CB Setting 70)
when freeze cycle termination temperature (CB Setting 2)
is met.
0 to 30 sec.
(1 sec. increments)
0
Water Tank
Ice Control
& Harvest
Cycle Low
Temperature
Control
74 Water Tank Ice Control Lower Temperature
See CB Setting 70, 71, 72, 74 description above.
Harvest Cycle Low Temperature Control
If control board thermistor temperature at the beginning of
harvest cycle is equal to or less than the harvest cycle low
temperature control setting, hot gas valve repeatedly
energizes for 40 seconds then de-energizes for 40 seconds
to promote a balanced harvest across the evaporator plate.
0 to 40°C
(1°C increments)
0