1-Minute Fill Cycle – LED 4 is on. WV energizes. After 1 min., CB checks for a closed
FS. If FS is closed, harvest cycle begins. If harvest cycle begins (Comp, HGV, and FMR
energize), continue to step 5. If FS is open, WV remains energized through additional
1-min. fill cycles until water enters the water tank and FS closes (low water safety
protection during initial start up and at the end of each harvest).
Diagnosis: Check
that water enters the water tank. If not, check that the water supply line shut-off valve
is open and screens or external filters are clear. Check for 115VAC at CB K1 #6 (O)
to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV
does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity.
If open, replace WV. If the water tank fills, but the appliance fails to start harvest (Comp
energized), check for open FS. See "II.E. Float Switch Check and Cleaning." If FS is
closed and CB fails to start the harvest cycle after 1 min., replace CB.
5)
Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV continues. Comp, FMR, and
HGV energize. CB monitors the warming of the evaporator via the thermistor located
on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the
thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2).
The harvest timer has settings of 60, 90, 120, and 180 sec. The pump-out timer (S4 dip
switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out (S4 dip
switch 5 & 6). WV remains energized during harvest for a maximum of 6 min. or the
length of harvest, whichever is shorter.
a)
Comp Diagnosis: Check that evaporator is warming. If not, confirm that Comp
energizes. If not, check for 115VAC at CB K1 #1 or #9 (V) to neutral (W). If 115VAC is
not present, check for 115VAC at CB K1 #7 or #10 (BR) to neutral (W). If 115VAC is
present at #7 or #10 (BR) and not at #1 or #9 (V), replace CB. If 115VAC is present,
check for 115VAC at CR or MC solenoid. If 115VAC is present, confirm contacts are
closed. If not, replace CR or MC. If CR or MC contacts are closed, check Comp
external overload, Comp start and run capacitors, Comp start relay, and Comp motor
winding.
b)
HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W).
If 115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV
coil and check HGV coil continuity. Replace as needed.
c)
LLV Diagnosis: Confirm that LLV is de-energized and closed (not bypassing).
If energized, replace CB. If de-energized and bypassing, replace LLV.
d)
WRV Diagnosis: Confirm WRV is not leaking by.