28
No.
Item
Display (example)
5
Ambient temp correction
rate for integrated value
90%
100% (last 2 digits
only)
6
Freeze backup timer
Same as No. 3
10
Defrosting water supply
time, water temp less than
13°C
Same as No. 3 (unit: sec)
11
Defrosting water supply
time, water temp 13°C or
more
Same as No. 3 (unit: sec)
12
Icemaking water supply
time, normal
Same as No. 3 (unit: sec)
13
Water temp measurement
correction value
Same as No. 1
14
Full / partial drain lush
selection
Same as Nos. 21 and 22
15
Additional icemaking water
supply time
Same as No. 3 (unit: sec)
17
Defrosting water control
Same as Nos. 21 and 22
18
Defrost completion temp
correction
Same as No. 1
21
Double stack bin control
0
1
22
Refrigeration unit operation
in bin control cycle
30
Model type
Same as Nos. 21 and 22
(Setting range from 0 to 3)
34
Defrost cycle low temp
control, operating temp
Same as No. 1
36
Water regulator error
detecting temp
Same as No. 1
37
Compressor output
selection
Same as Nos. 21 and 22
50
Slush ice, pump off time
Same as No. 3 (unit: sec)
51
Slush ice, water supply time
Same as No. 3 (unit: sec)
60
Hard water, operating
condition
Same as No. 5
61
Hard water, water supply
time
Same as No. 3 (unit: sec)
70
Ice left in water pan,
operating temp
Same as No. 1
71
Ice left in water pan, hot
gas valve on time
Same as No. 3 (unit: sec)
73
Ice bridge, hot gas valve off
time
Same as No. 3 (unit: sec)
74
Low temp in defrost cycle,
operating temp
Same as No. 1