Electrical Setting Page 2
Bypass Voltage Range: Set the bypass voltage range.
L
: Low voltage point for bypass. The setting range is 176V ~ 205V. 176V is
default setting.
H
: High voltage point for bypass. The setting range is 235V ~ 264V. 264V is
default setting.
Bypass FREQ Range: Set the bypass frequency range.
L
: Low frequency point for bypass. The setting range is 45Hz ~ 49Hz for 50Hz
system and 55Hz ~ 59Hz for 60Hz system. 46Hz is default setting for 50Hz
system and 56Hz is default setting for 60Hz system.
H
: High frequency point for bypass. The setting range is 51Hz ~ 56Hz for 50Hz
system and 61Hz ~ 66Hz for 60Hz system. 54Hz is default setting for 50Hz
system and 64Hz is default setting for 60Hz system.
ECO Mode: Enable/Disable ECO mode. Default setting is “Disable”.
ECO Voltage Range: Set the ECO voltage range.
L
: Low voltage point for ECO mode. The setting range is 176V ~ 210V. The
default setting is 205V.
H
: High voltage point for ECO mode. The setting range is 230V ~ 264V. The
default setting is 235V.
ECO FREQ Range: Set the ECO frequency range.
L
: Low frequency point for ECO mode. The setting range is 45Hz ~ 49Hz for
50Hz system and 55Hz ~ 59Hz for 60Hz system. The default setting is 48Hz for
50Hz system and 58Hz for 60Hz system.
H
: High frequency point for ECO mode. The setting range is 51Hz ~ 56Hz for
50Hz system and 61Hz ~ 66Hz for 60Hz system. The default setting is 58Hz for
50Hz system and 62Hz for 60Hz system.
Summary of Contents for Orion Series
Page 16: ...14 The wire terminals of each model are shown as below 10K 30K 40K 60K 80K 120K 160K 200K ...
Page 28: ...26 Turn On Off UPS Turn On UPS Turn Off UPS Battery Test Do Battery Test ...
Page 29: ...27 Cancel Battery Test Audio Mute Active Audio Mute Cancel Mute ...
Page 46: ...44 Initial Initial Setting Menu Page Data Log Initial Page Parameters Initial Page ...