Auto Restart: Enable/Disable auto-restart function.
Enable
: Enable the auto-restart function. If selected, once UPS shutdown
occurs due to running out of battery and then utility restores, the UPS will
return to line mode. The default setting is “Enable”.
Disable
: Disable the auto-restart function. If selected, once UPS shutdown
occurs due to running out of battery and then utility restores, the UPS will not
restart.
These two parameters are related to the “S.D & R” on the “CONTROL” sub-menu. If
executing “S.D & R” action, the UPS will shut down and restore according to the setting
of system shutdown time and system restore time here. For example, if the system
shutdown time is 1 min, the system restore time is 2 min, it means the UPS will shut
down in 1 minute and wait for 2 minutes, then restart again.
Shutdown Delay Second: Set the system shutdown time. The setting range is 1 sec. ~
9999 sec. The default setting is 1 second.
Restore Delay Minute: Set the system restart time after shutdown. The setting range is
1 minute to 9999 minutes. The default setting is 1 minute.
New Password: Modify password.
No
: No change for password.
YES:
Modify the password.
Service Setting
Password Page