40
Output PF:
Setting output power factor. There are two options: 0.8 and 0.9. If
power failure occurs, the setting will become default.
No Bat On Load:
En:
If selected, the UPS could operate on AC mode without battery, but it will show
“battery is not connected” as reminder.
Note:
In this mode, when the AC input is unstable, the UPS will enter to bypass
mode. If bypass voltage is unstable or no input on bypass, there is risk of power
failure for the loads.
Maintenance to Remind:
Setting the maintenance time. There are four options, Never, 3 months, 6 months
and 1 year. “Never” is the default setting. When setting time is up, it will show a
warning of “Need to maintain” in the LCD screen. If the time is not up and you re-
set up the timer, it will calculate the time from the beginning.
Show Real Power
Yes:
It’s allowed to show real power information on “Information” menu.
No:
It’s not allowed to show real power information on “Information” menu.
OP S-C to BPY
En:
When enabled, it allows UPS to transfer to bypass mode while output short
circuit occurs.
Dis:
When disabled, it doesn’t allow UPS to transfer to bypass mode while output
short circuit occurs.
System Parameter Setting Page 3
Float Voltage:
Setting float voltage. The setting range is from 9.0V to 15.0V. The
default setting value is 13.5V.
CV Charge Time:
Setting charge time for constant voltage. Setting time range is
from 1 to 900 minutes.
Auto:
It will automatically adjust based on charging voltage and current.
Cycle Charge Time:
Setting frequency to activate constant charging voltage. The
setting range is 1~12 months.
Auto:
It will automatically activate constant charging voltage based on charging
voltage and current.
Summary of Contents for Orion Series
Page 16: ...14 The wire terminals of each model are shown as below 10K 30K 40K 60K 80K 120K 160K 200K ...
Page 28: ...26 Turn On Off UPS Turn On UPS Turn Off UPS Battery Test Do Battery Test ...
Page 29: ...27 Cancel Battery Test Audio Mute Active Audio Mute Cancel Mute ...
Page 46: ...44 Initial Initial Setting Menu Page Data Log Initial Page Parameters Initial Page ...