Wireless Room Thermostat 

 

       

HTW-31-WKT13-WF

 

                   

 

                                                                                       

When the Open Window detect function is enabled in the parameter setting, the system will automatically stop heating 

when it detects a sudden drop of room temperature (2°C in 15 minutes as default). This is normally caused when a 

window or door is opened without turning off the heating device.   

The device will return to the previous mode of operation after 30mins, then 

OP

 disappear. Press any button will exit OWD 

function during the heating off period. 

 
Parameter Setting 

 

Under off mode, press and hold 

SET

 button and 

+

 button for 6s to enter parameter setting.    Each press of 

SET 

button will 

go to next item setting. Adjust the value by pressing 

+

 or 

 button. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring Diagram       

 

 

 

 

 

 

 

 

 

 

Menu

 

    Description   

 

Range 

Default Value 

01

 

Temp. calibration for internal sensor           

 

-8 

 ~8 

 

  0

 

02 

Set Point Max. 

 ~35

 

35 

 

03 

Set Point Min. 

 ~35

 

 

05 

Frost Protection Temp. 

 ~15

 

 

09 

Dead zone 

0~3

 

0

 

10 

Display 

0: Room temp. 

1: SET temp. 

12 

Open window detect function 

1: Enable    0: Disable   

  0 

13 

OWD Detect Time   

2~30mins 

  15mins 

14 

OWD Drop temp. select 

within detect time

 

2.3.4

‟C 

  2 

„C 

15 

OWD Delay time select 

(Return to previous working status) 

10~60min 

  30mins   

17 

Factory reset 

0: No 

  0   

1: Yes, and then press 

On/off  button  for  5s,wait 

until thermostat restart   

18 

Software version   

7109 

 