Smart Wifi Fan Coil Thermostat
Reference No.:
HTW-WF01-FC Series
- 4 -
Version 2018-1.0
The installation personnel with non-professional training shall not perform this operation!
During thermostat power off, Press these 2 buttons M & simultaneously and hold for 5 seconds to enter
ISU process. Press to adjust the configurable parameter value, and press M to switch to next parameters.
The ISU process will automatically exit and be confirmed after 5 seconds with no operation.
Parameter
Function
Configurable Value
Default
1
Temperature calibration
-7°C to +9°C (internal sensor)
-1
2
Fan Control Type
00:When room temp. reaches set point, the fan turns off
01:When room temp. reaches set point, the fan turns to low
00
3
Keypad Lock type
00: = All buttons will lock except the Power button
01: = All buttons will lock
01
4
Heating/Cooling
00: Cool only 01:Heating and Cooling
01
5
Min. set-point limit
5°C - 15°C
05
6
Max. set-point limit
15°C - 45°C
35
7
12/24 hours format
00:12h 01:24h
01
8
Temperature Display
00
:
display both set-point and room temp.
01
:
display set-point only
00
9
Economy Mode
00
:
Normal mode
01
:
Energy Saving mode
00
A
Heating Economy
Temperature
10°C - 30°C
20
B
Cooling Economy
Temperature
10°C - 30°C
26
C
Dead Zone
1°C to 5°C (Switching differential)
1
Products are warranted for 2 full year (checking and repairing
services) from the date of purchase which products are not
being damaged by any man-made factors.
Service outwith the warranty period may incur an extra charge.
More details please contact with Hotowell directly.
Warranty