HEALTH AND SAFETY

19. Working with a naked flame i.e. soldering or brazing is forbidden. Unless otherwise stated, 

pipework connections must only be made using the Lokring coupling system.

20. Electronic leak detectors with high voltage tips must NOT be used with any Isobutane (R600a).

21. All equipment used for this activity must be checked regularly and maintained in a safe working 

condition; parts must be replaced as required.

Information Regarding Isobutane Canisters

1.

The maximum quantity of Isobutane an engineer should hold or store at any one time is two 1kg 
net aluminium canisters, supplied individually as Part Number 2602600.

2.

Canisters must be stored inside the aluminium case with the weighing scales for protection from 
possible damage and heat. The aluminium case must NEVER be placed next to a heat source or 
in direct sunlight.

3.

Isobutane must only be dispensed to the appliance from the 1kg net aluminium canister placed 
in an upright position on the weighing scales provided.

4.

All used canisters must be a returned as scrap and therefore, left out for the driver to collect and 
return for disposal.

5.

Canisters must not be punctured or the internal valve damaged.

6.

Before storing the canister it must have the extraction tap valve removed and the internal valve 
of the canister checked for leakage using leak detector (Leak Detector: Part Number 5700043).

7.

All used canisters and those found to be leaking should be exhausted to atmosphere to ensure 
they are emptied completely. Refer to the following paragraph.

8.

Refit the extraction tap if necessary, open the tap and then invert the canister.
This must be done outside in open air away from buildings and ignition sources and complying 
with Item 18 on previous page.

THERMOSTAT REPLACEMENT

All replacement thermostats must have the capillary phial taped/insulated where it is routed past any 
electrical terminations, in the same way as the original one fitted to the appliance.
Replacement thermostats will not have the insulating tape already fitted and this MUST be done 
before the work is completed.

Summary of Contents for RZ150G

Page 1: ...Company UK Ltd 2007 Reg Office Peterborough PE2 9JB Registered in London 106725 Service Information HOTPOINT FREESTANDING FREEZERS Model Comm Covered Code RZ150P 44354 RZ150G 44355 5407383 Issue 1 Ma...

Page 2: ...dless power tools are forbidden within the storage area working area and vehicles used to transport Isobutane 9 The carrying case for the scales and refrigerant must display a red flammability label P...

Page 3: ...t aluminium canister placed in an upright position on the weighing scales provided 4 All used canisters must be a returned as scrap and therefore left out for the driver to collect and return for disp...

Page 4: ...Bruto Brut Compr Kompr Syst R 134 a kg 0 090 Gross Bruto Brut 340 Net Util Utile Gross Bruto Brut Freez Capac Poder de Cong 75 Made in 13918 Test P S I Pressure HIGH 235 LOW 140 kg 24 h 4 0 Class Cla...

Page 5: ...ic design so defrosting is actioned manually When the user defrosts the freezer the defrost water drains into the liner base and is channelled to a drain hole exiting through a spout moulded into the...

Page 6: ...band models 40dB Climate Class Rating Plate A band SN N ST 10 C to 38 C Refrigeration Type Static Wire On Tube WOT DIMENSIONS WEIGHT Models RZ150 Height 1500 mm Width 600 mm Depth 655 mm Weight Gross...

Page 7: ...uency 50 Hz Absorption Current Normal Operation 0 7 Amps COMPRESSOR WINDING Manufacturer JIAXIPERA Type I D ZBT1114CY Winding Resistance Start 16 0 Run 13 3 Refrigerant Grams R600a Refer to the applia...

Page 8: ...OF APPLIANCE TEMPERATURE CONTROL PANEL APPLIANCE INTERIOR SUPER FREEZE Button SUPER FREEZE Indicator Lamp ALARM Indicator Lamp TEMPERATURE Control Knob POWER Indicator Lamp FREEZER and STORAGE Compart...

Page 9: ...9 of 15 Indesit Company Service Manual UK English NOTES...

Page 10: ...anual Read the instructions on the next page fully and refer to the diagrams below before carrying out the door reversal Also before commencing the door reversal you will require the left door closure...

Page 11: ...xing plate Transfer them to the other side Remove the hinge pin from the right hand side of the hinge and retain until the plinth is in place Insert the plinth blanking plate supplied with the applian...

Page 12: ...ed 4 Brown Thermostat 3 5 Black Thermostat 4 6 Green Yellow Earth 1 Not Used 2 Blue Neutral 3 Not Used 4 Brown Live 5 Black Compressor Overload 6 Green Yellow Earth Yellow Super Freeze Switch 3 THERMO...

Page 13: ...erminal 1 and Control Harness Plug 4 4 CONTROL PANEL INDICATOR LAMPS Alarm Indicator Lamp Red Thermostat 6 Blue Neutral Link to Power Indicator Lamp Blue Control Harness Plug 2 Power Indicator Lamp Br...

Page 14: ...it Company English THEORETICAL WIRING DIAGRAM ELECTROLUX ACC ZEM JIAXIPERA COMPRESSORS OVERLOAD COMPRESSOR SUPER FREEZE INDICATOR LAMP POWER INDICATOR LAMP CAPACITOR if fitted SUPER FREEZE SWITCH ALAR...

Page 15: ...anual UK English PARTS and ACCESSORIES To order parts and accessories contact our National Mail Order Parts Hotline 08709 077 077 Monday to Friday 8 00am to 5 30pm Saturday 8 30am to 12 00 noon or onl...

Reviews: