Page 9
230 VOLT SUBPANEL WIRING INSTRUCTIONS
(
T
EMPO
,
R
ELAY
&
R
HYTHM
)
NOTE
: The subpanel must be placed within 100 feet (30.5m) of the main electrical service panel, and between 5 (1.5 m) and 50 feet (15 m) away
from the spa. All electrical connections must be made in accordance with the wiring information contained in this manual and on the back of the
field wiring access panel of the control box.
Refer to the wiring diagram below.
1. Connect the #8 AWG, WHITE [NEUTRAL] wire from the Neutral/Ground Bar on the main electrical service to the WHITE [NEUTRAL, Panel
Neutral, Pigtail] of the subpanel.
2. Connect the #8 AWG, BLACK [L1] wire from the main electrical service to the subpanel [terminal L1].
3. Connect the #8 AWG, RED [L2] wire from the main electrical service to the subpanel [terminal L2].
4. Connect the #10 AWG, GREEN wire from the Neutral/Ground Bar on the main electrical service to the GROUND terminal of the subpanel.
5. Connect the #8 AWG, WHITE [NEUTRAL] wire from the subpanel breaker to the Neutral terminal on the spa’s control box.
6. Connect the #8 AWG, BLACK [L1] wire from the subpanel breaker to terminal [L1] on the spa’s control box.
7. Connect the #8 AWG, RED [L2] wire from the subpanel breaker to terminal [L2] on the spa’s control box.
8. Connect the #10 AWG, GREEN wire from the GROUND terminal of the subpanel to the GROUND terminal in the spa’s control box.
9. Bond the spa to all exposed metal equipment or fixtures, handrails, and concrete pad per N.E.C. and all local codes.
PERMANENTLY CONNECTED 230
VAC, 40A, 60Hz, MODELS
*ALL CANADIAN SPA MODELS USE #8 AWG GREEN, GROUND.
THESE SPAS ARE INTENDED FOR USE WITH GFCI SUBPANEL PROVIDED.
MORE THAN 5 FEET
THE SUBPANEL MUST
BE WITHIN SIGHT OF THE
SPA DO NOT EXCEED
50 FEET
SUBPANEL
WITH GFCI
BREAKERS
MAIN
SERVICE
ELECTRICAL
PANEL
230VAC, 50 AMP
2-POLE
CIRCUIT
BREAKER
(NON GFCI)
LESS THAN 100 FT.
#8 AWG WHITE, NEUTRAL
#10* AWG GREEN, GROUND
#8 AWG BLACK, L1
#8 AWG RED, L2
N, NEUTRAL, #8 AWG WHITE
GROUND, #10 AWG GREEN*
L1, HOT, #8 AWG BLACK
L2, HOT, #8 AWG RED
CONTROL BOX
Electrical Installation
Page 9