Page 29
GLEAM
- WIRING INSTRUCTIONS
ELECTRICAL REQUIREMENTS AND
PRECAUTIONS
Your spa has been carefully designed to give you maximum safety against
electrical shock. Connecting the spa to an improperly wired circuit will negate
many of the spa’s safety features. Improper wiring may also cause electrocution,
risk of fire, and other risks of injuries. Please read and follow the electrical
installation requirements and instructions for your spa completely! Unless
otherwise stipulated by your dealer,
THIS IS YOUR RESPONSIBILITY
.
SERVICE NOTE
: All
HOT SPRING
spas have diagnostic functions
that are displayed on the main control panel when the Power Indicator,
Ready Indicator or both are blinking. Follow the instructions in the
troubleshooting section to identify and correct the cause.
HOT SPRING
SPAS MUST BE WIRED IN ACCORDANCE WITH ALL
APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES. ALL
ELECTRICAL WORK SHOULD BE DONE BY AN EXPERIENCED,
LICENSED ELECTRICIAN. WE RECOMMEND THE USE OF
APPROPRIATE ELECTRICAL CONDUIT, FITTINGS, AND WIRE FOR
ALL CIRCUITS.
NOTE
: The
GLEAM
will require an additional 16 amp breaker in order
to operate the heater and jet pump 3 at the same time. Without the
additional 16 amp breaker, the heater will NOT operate while jet pump 3
is on (see back of the control box lid for wiring information).
Mount the subpanel according to local codes, but not closer than 1.5
meters (5 feet) away.
CONDUIT INSTALLATION INSTRUCTIONS
1. To connect the electrical service, first remove the screws from the
equipment compartment door.
2. Locate the control box. Loosen the screws on the front of the
control box. Remove the screws and the control box cover.Route
the electrical service from the subpanel into the spa equipment
compartment using the cut out in the frame below the door.
3. Connect the supply conduit to the control box and connect the
wiring as detailed below and on the wiring diagram label on the
inside of the control box cover.
WARNING
: Removing or bypassing any GFCI breaker will result in
an unsafe spa and will void the spa’s warranty.
IMPORTANT
: Should you ever find the need to move or relocate your
spa, it is essential that you understand and apply these installation
requirements. Your spa has been carefully engineered to provide
maximum safety against electric shock. Remember, connecting the spa
to an improperly wired circuit will negate many of its safety features.
IMPORTANT:
Service Technician must reconfigure spa using the soft
jumpers to allow spa heater to run concurrent with jet pump if a second
16 amp breaker is installed.
NOTE
: Long wiring runs may require larger-gauge wire than stated.
Electrical Requirements
NOTES:
Connect supply wiring as shown in the diagrams above.
Connect only to a circuit which is protected by a Ground Fault Circuit Interrupter (GFCI).