Fit access panel again and return isolation switch to 'On'
position.
RoofVent
®
LHW, LKW, condens, direct cool
RoofVent
®
twin heat/cool/pump:
RoofVent
®
LH, LK
Weather louvre door
Fresh air filter
Access panel
Extract air filter
Table N1: Position of the filters in the RoofVent
®
units
2.3 Inspection and maintenance work
Caution
Risk of injury if work is not performed appropriately.
Inspection and repair work must be carried out by
Hoval customer service personnel !
The following work is carried out during the annual inspec-
tion:
■
Cleaning of the units
■
Fan and actuator function tests
■
Function testing of the control systems
■
Where siphons are fitted: testing of the odour seal.
■
On the RoofVent
®
condens: Check system pressure, frost
protection, pH value, burner and ignition electrode.
■
On the RoofVent
®
condens: Replace neutraliser cartridge.
The following work is carried out every 3 years:
■
On the RoofVent
®
condens: Check inhibitor protection.
Condensate pump (optional)
On RoofVent
®
units equipped with a condensate pump:
■
Check condensate pump every two months during the
cooling period and clean it if required.
2.4 Repairs
Caution
Risk of injury is work is not performed appropriately.
Repair work must be carried out by Hoval customer
service personnel !
Please contact Hoval customer service if needed.
Operation
Maintenance and repair
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......