Three-Phase Padmounted Distribution Transformers
Transformer Storage
Transformers may be temporarily stored if properly
prepared. It is recommended that transformers
be stored completely assembled. Prior to storage,
transformers should be thoroughly inspected as
described above in the “Initial Inspection” section.
If the transformer is not completely assembled,
separate components and accessories should be
stored in a clean dry area in their original shipping
containers. Do not store the transformer in a
corrosive environment.
If the transformer is to be stored for an extended
period of time before being placed into service,
it should be stored on a firm level surface. The
gas space above the insulating fluid should be
pressurized with dry nitrogen to a pressure of 2-3
PSIG. This will prevent a negative internal pressure
that might draw moisture into the tank.
It is recommended that the transformer be
inspected periodically while it is in extended
storage. Ensure that an effective pressure seal
is maintained, and check for leaks and corrosion.
Any damage or defects should be repaired
immediately.