background image

 

 

 

ISRB

 2005 GEA 20260

 

Page 10 of 24

 

temperature change, installation of flexible 

connectors or expansion joints is advisable. 
Figure 1, page 12 for Whispair Max and Figure 2, 

page 14 for DVJ blower represents an installation 

with all accessory items that might be required under 

various operating conditions. Inlet piping should be 

completely free of valves or other restrictions. When 

a shut-off valve cannot be avoided, make sure a full 

size vacuum relief is installed nearest the unit inlet. 

This will protect against unit overload caused by 

accidental closing of the shut-off valve. 
Need for an inlet silencer will depend on unit speed 

and pressure, as well as sound-level requirements in 

the general surroundings. An inlet filter is 

recommended, especially in dusty or sandy locations. 

A discharge silencer is also normally suggested, 

even though Whispair units operate at generally 

lower noise levels than conventional rotary blowers. 

Specific recommendations on silencing can be 

obtained from your local Howden Roots distributor. 
Discharge piping requires a pressure relief valve, and 

should include a manual unloading valve to permit 

starting the unit under no-load conditions. Reliable 

pressure/vacuum gauges and good thermometers at 

both inlet and discharge are recommended to allow 

making the important checks on unit operating 

conditions. 
In multiple unit installations where two or more units 

operate with a common header, use of check valves 

is mandatory. These should be of a direct acting or 

free swinging type, with one valve located in each 

line between the unit and header. Properly installed, 

they will protect against damage from reverse 

rotation caused by air and material back-flow through 

an idle unit. 
After piping is completed, and before applying power, 

rotate the drive shaft by hand again. If it does not 

move with uniform freedom, look for uneven 

mounting, piping strain, excessive belt tension or 

coupling misalignment. 
DO NOT operate the unit at this time unless it has 

been lubricated per instructions. 

 
 

Lubrication 

Due to sludge build-up and seal leakage problems, 

Roots recommendation is DO NOT USE Mobil SHC 

synthetic oils in Roots blowers. 
2500 Series blowers gear end bearing lubrication. 

 

The specified and recommended oil is Roots 

Synthetic oil of correct viscosity per Table 1, 

page 9. 

 

To fill the gearbox, remove the oil fill plug (140) 

and the oil level plug (111) - see page 8. Fill the 

reservoir up to the overflow hole. DO NOT 

OVERFILL. Place the breather and the overflow 

plug back into their respective holes. 

 

The lubrication should be changed after initial 

100 hours of operation. 

 

If you choose to use another oil other than the 

specified and recommended Roots Synthetic, 

use a good grade of industrial type non-

detergent, rust inhibiting, anti-foaming oil and of 

correct viscosity per Table 1, page 9. 

 

Roots does NOT recommend the use of 

automotive type lubricants, as they are not 

formulated with the properties mentioned above. 

 

Proper service intervals of the oil thereafter are 

based on the discharge air temperature of the 

blower. Please refer to the information below to 

“How to properly determine the oil service 

intervals.” 

How to properly determine the oil service 

intervals:  

Normal life expectancy of the specified and 

recommended Roots Synthetic oil is approximately 

6000 hours with an oil temperature of 180°F (82°C) 

or less. As the oil temperature increases by 

increments of 15°F (8°C), the oil life is reduced by 

half for each 15°F (8°C) increase. Example: Oil 

temperatures of 195°F (90.5°C) will produce a life 

expectancy reduced by half or 3000 hours oil service 

life. 
Normal life expectancy of petroleum based oils is 

about 2000 hours with an oil temperature of about 

180°F (82°C). As the oil temperature increases by 

increments of 15°F (8°C), the life is reduced by half 

for each 15°F (8°C) increase. Example: Oil 

temperatures of 195°F (90.5°C) will produce life 

expectancy reduced by half or 1000 hours oil service 

life. 

ISRB 2005 GEA 20260.indd   10

17/09/2015   12:53

Summary of Contents for Roots 2500 Series WHISPAIR MAX

Page 1: ...oots 2500 Series WHISPAIR MAX Blowers and DVJ Blowers Installation Operation and Maintenance Manual www howden com Installation Operation and Maintenance Manual Roots 2500 Series WHISPAIR MAX Blowers...

Page 2: ...ation Provide for adequate safeguards against accidents to persons working on or near the equipment during both installation and operation See SAFETY PRECAUTIONS Install all equipment correctly Founda...

Page 3: ...rmance Warranty is contingent on such operation Maximum limits for pressure temperature and speed are specified in Table 2 page 9 for Whispair Max and Table 3 page 9 in the 2500 Series DVJ Section for...

Page 4: ...lled and workable 7 Open the manual unloading valve in the discharge air line If a valve is in the inlet piping be sure it is open 8 Bump blower a few revolutions with driver to check that direction o...

Page 5: ...rmined through spectral analysis As shown on the chart below the level of all pass vibration will determine the need to measure discrete frequency vibration levels and the action required Installation...

Page 6: ...he impellers turn freely at all points Anti rust compound on the connection flanges and drive shaft extension may also be removed at this time with the same solvent Cover the flanges until ready to co...

Page 7: ...g manufacturer s recommendations for maximum misalignment although acceptable for the coupling are normally too large to achieve smooth operation and maximum life of the blower The following requireme...

Page 8: ...TE Arc of sheave belt contact on the smaller sheave not to be less than 170 Driver to be installed on the inlet side for vertical units and on the drive shaft side for horizontal units ROOTS recommend...

Page 9: ...RECT COUPLED to its driver the driver RPM must be selected or governed so as not to exceed the maximum speed rating of the unit Refer to Table 1 for allowable speeds of various unit sizes The driver s...

Page 10: ...unting piping strain excessive belt tension or coupling misalignment DO NOT operate the unit at this time unless it has been lubricated per instructions Lubrication Due to sludge build up and seal lea...

Page 11: ...traces of clean grease comes out of the relief fitting The use of an electric or pneumatic grease gun could force the grease in too rapidly and thus invert the seals and should not be used Gear end b...

Page 12: ...ervice life A newly installed blower should be checked often during the first month of full time operation Attention thereafter may be less frequent assuming satisfactory performance Lubrication is no...

Page 13: ...ng This is indicated by unusually high temperature at the bottom of the gear housing Consequent heating of the gears will result in loss of tooth clearance backlash and rapid wear of the gear teeth us...

Page 14: ...ISRB 2005 GEA 20260 Page 14 of 24 Troubleshooting Checklist...

Page 15: ...ISRB 2005 GEA 20260 Page 15 of 24 2500 Series WHISPAIR Max Blowers...

Page 16: ...n 18 5 Hg and a gear speed below 3650 feet per minute Jet and discharge flow restrictions result in increased blower temperature rise and should be checked as a possible cause if the temperature rise...

Page 17: ...ISRB 2005 GEA 20260 Page 17 of 24 NOTE One cylinder slot plenum must have a full size inlet silencer with no valve or other restrictions The other port must have the 2 countersunk pipe plug installed...

Page 18: ...per or tape Trouble Shooting Check List This list in standard instructions applies except note that in those lists and in various locations throughout the standard instruction manuals for uncoated mac...

Page 19: ...east 70 F allow each coat to cure at least overnight in shop ambient not warehouse or outdoors Alternate 3 Cure in oven or by other source of even heat not flame for 10 minutes minimum at a temperatur...

Page 20: ...ISRB 2005 GEA 20260 Page 20 of 24...

Page 21: ...ISRB 2005 GEA 20260 Page 21 of 24 Assembly of 2500 Series WHISPAIR Max Blower...

Page 22: ...ISRB 2005 GEA 20260 Page 22 of 24 Assembly of 2500 Series DVJ Blower...

Page 23: ...ISRB 2005 GEA 20260 Page 23 of 24...

Page 24: ...prove our products and services and for over 160 years our world has revolved around our customers This dedication means our air and gas handling equipment adds maximum value to your operations We hav...

Reviews: