QuickSpecs

hp Modular Power Distribution Units

(Zero-U/1U Modular PDUs)

DA-11041

World Wide — Version 3 — December 11, 2002

2

O

V E R V I E W

Modular PDUs have a unique modular architecture designed specifically for the dense data center customers who want to maximize their power

distribution and space efficiencies in the rack. This new modular design consists of two main building blocks, the Control Unit and the Extension Bar(s).

Available in 16A-40A current ratings, each unit comes with one Control Unit and up to four Extension Bars, offering up to 32 outlet receptacles (the 16A

model has two Extension Bars, and offers 16 outlets).

 

Providing easy accessibility and reduced cable clutter, the Modular PDUs offer you the flexibility to

easily mount your units in several different locations within the rack, without having to sacrifice valuable rack U-space.

K

E Y  

F

E A T U R E S

 

Unique modular design architecture

 

Small form factor with flexible mounting options

 

Up to 32 outlet receptacles

 

Easy installation

 

Consolidate and maximize cord management

 

Easily accessible outlets

 

Current ratings from 16A to 40A

P

R O D U C T  

H

I G H L I G H T S

Unique Modular Design Architecture

Modular PDUs have a unique modular design architecture. This “Building block” concept consists of two main parts, the Control Unit, and the Extension

Bar(s). The 24-40A mPDUs ship with one Control Unit and 4 Extension Bars. Each Control Unit is a single-phase unit that branches out into 4 single-

phase branch circuits. The Extension Bars can be plugged into the Control Unit, and can be mounted directly to the rack frame, spanning the entire length

of the rack.

Note: The new 16A Modular PDU model ships with one Control Unit (with 2 branch circuits) and two Extension Bars. This is the only model in the Modular

PDU family that has a detachable input power cord, allowing for increased flexibility, ease of use, and adaptability for country specific requirements.

The 24A and 32AmPDU models come with an attached input power cord, due to regulatory requirements for higher amperage devices. And the 40A

model has to be field wired. Higher amperage mPDUs offer more outlets, allow more equipment to be connected, and are especially suited to the

high-density server deployments.

Small Form Factor and Flexible Mounting Options

The Control Unit is zero-U or 1U rack mountable. And the Extension Bars mount directly to the rack-frame or the rack extension unit. With each Modular

PDU, you can get up to 32 outlet receptacles (except for the 16A and 40A models) in zero-U of rack space. And if you plan to mount two Modular PDUs in

one rack (typical configuration), you could get up to 64 output receptacles, without having to use any rack U-space.

Up to 32 Outlet Receptacles

Modular PDUs offer up to 32 outlet receptacles. Meaning, customers can plug-in as many as 32 power cords into one Modular PDU set. And if they were

to mount two such PDU sets, they have a total of 64 outlets! That means the Modular PDUs can support anywhere from a couple of servers in a rack to

up to 42 1U servers (IMPORTANT: Provided the total current load does not exceed the maximum allowable current draw of the PDU. To calculate server

current draw, please refer the Proliant Power calculator on

 

ActiveAnswers System Configurator tool).

Note: The 16A model has 16 outlets and the 40A model has 28 outlets, while the other models have 32 outlets.

Easy Installation

The installation process is quick and easy. Whether you choose to mount the Modular PDU in zero-U or 1U, all required mounting brackets, accessories,

and installation instructions are shipped with the product. The Extension Bars come with easy to use, snap-in brackets, which fit directly into the rack

frame of a HP 9000 and 10000 Series racks.

Note: Modular PDUs may be installed in most third-party racks in a 1U configuration (no zero-U mounting). To mount the Extension Bars in a rack other

than the HP 9000 and 10000 series racks, an optional kit PN 310777-B21 is offered. This kit allows mounting the Extension Bars in most third party

racks that use a standard EIA19

 vertical rail.

Summary of Contents for 16A

Page 1: ... PDU Model s 200 240 VAC 16A Model mPDU 16A High 252663 B24 WW 24A Model mPDU 24A High 252663 D72 NA LA JPN 32A Model mPDU 32A High 252663 B31 INT L 40A Model mPDU 40A High 252663 B21 WW Feature List Single input power distribution units with a unique modular design architecture Up to 32 outlet receptacles Zero U 1U dense rack form factor Easily accessible outlet receptacles and improved cable man...

Page 2: ... models come with an attached input power cord due to regulatory requirements for higher amperage devices And the 40A model has to be field wired Higher amperage mPDUs offer more outlets allow more equipment to be connected and are especially suited to the high density server deployments Small Form Factor and Flexible Mounting Options The Control Unit is zero U or 1U rack mountable And the Extensi...

Page 3: ... out devices Current Ratings from 16A to 40A Modular PDUs are available in a wide range including four high volt models ranging from 16A to 40A current ratings and one low voltage 24A model Compatibility Ideal for use with the HP 9000 and 10000 Series Racks the Modular PDUs are largely designed for the dense rack environment These Modular PDUs connect directly to the facility input power In additi...

Page 4: ...o 60 C Storage Relative Humidity 5 to 95 Storage Elevation 0 to 30 000 ft 0 to 9144 m Conformance Standards UL CUL CE NOM D 16A and 40A models UL CUL NOM 24A High and Low voltage models CE D 32A model Kit Contents 24 40A Modular PDUs ship with x1 Control Unit and x4 Extension Bars 16A Modular PDU ship with x1 Control Unit and x2 Extension Bars All models ship with 0U 1U Mounting brackets hardware ...

Page 5: ...ea Input 3 6m attached cable with L6 30P Output Four IEC320 C19 12A ea Input 3 6m attached cable with IEC309 32A Output Four IEC320 C19 12A ea Input Hardwire Output Four IEC320 C19 12A ea Note Manual ON Off control provided for each load group switch guards provided to prevent inadvertent power Off The Control unit for the 16A model has 2 outputs while the Control Unit for all other Modular PDUs h...

Page 6: ...Bars while all other 24 40A models ship with 4 Extension Bars 32 IEC 320 C 13 32 IEC 320 C 13 24 IEC 320 C 13 4 IEC 320 C 19 Applications Connects to low voltage models of the UPS R3000 XR and may also be connected directly into the facility input Connects to the high voltage models of the UPS R3000 XR and R6000 Note Except for the UPS R3000 XR North America high volt model where an additional cab...

Page 7: ...uired on the PDU for connecting the RILOE cards Please refer to the Power Cord Matrix for more information on power cords cable part numbers input output descriptions ftp ftp compaq com pub products servers proliantstorage power protection powercordmatrix pdf 2002 Hewlett Packard Company Hewlett Packard the Hewlett Packard logo CarePaq ProLiant and StorageWorks are trademarks of Hewlett Packard Co...