QuickSpecs

hp Modular Power Distribution Units

(Zero-U/1U Modular PDUs)

DA-11041

World Wide — Version 3 — December 11, 2002

6

M

O D U L A R  

P D U   F

A M I L Y  

I

N F O R M A T I O N

MODEL SELECTION MATRIX

Low Voltage 24A

High Voltage 16A

High Voltage 24A

High Voltage 32A

High Voltage 40A

Part Number

252663-D71

252663-B24

252663-D72

252663-B31

252663-B21

Input Connection

(Single Input)

NEMA L5-30P

Detachable input power
cord with a IEC 320-C20
inlet

Note: 

The 16A model with

the detachable cord can be
used only in applications

where the total leakage
current is less than 3.5 mA.

NEMA L6-30P

IEC 309-32A

Field Wired Terminal

Output Connections

(32) NEMA 5-15R

Note: The low volt Extension

Bars w/5-15 outlets should
be used ONLY with the low

volt Control Unit that is
shipped with the low volt

Modular PDU unit.

(16) IEC 320 C-13

Note: 

The 16A model ships

with 2 Extension Bars, while

all other 24-40A models ship
with 4 Extension Bars.

(32) IEC 320 C-13

(32) IEC 320 C-13

(24) IEC 320 C-13

(4) IEC 320 C-19

Applications

Connects to low voltage

models of the UPS R3000

XR (and may also be

connected directly into

the facility input)

Connects to the high
voltage models of the
UPS R3000 XR and
R6000

Note: 

Except for the UPS

R3000 XR, North America
high volt model, where an

additional cable option kit,
PN 340653-001 (IEC320-

C19 to L6-20P), is needed to
connect a 16A mPDU to the

NA high voltage model of the
UPS R3000 XR

Also connects directly into
the facility input

Note: 

You need to purchase

a cable PN 340653-001

(IEC320-C19 to L6-20P) for
North America. Other country

specific cables are managed
at the country level.

Designed to connect

directly into the facility

input

Designed to connect

directly into the facility

input

May be hardwired (

Note:

Hardwiring needs to be done

by a certified on-site
electrician in accordance with

the local electrical installation
codes.) 

into the facility

input or to a high voltage
UPS (R12000 XR)

Summary of Contents for 16A

Page 1: ... PDU Model s 200 240 VAC 16A Model mPDU 16A High 252663 B24 WW 24A Model mPDU 24A High 252663 D72 NA LA JPN 32A Model mPDU 32A High 252663 B31 INT L 40A Model mPDU 40A High 252663 B21 WW Feature List Single input power distribution units with a unique modular design architecture Up to 32 outlet receptacles Zero U 1U dense rack form factor Easily accessible outlet receptacles and improved cable man...

Page 2: ... models come with an attached input power cord due to regulatory requirements for higher amperage devices And the 40A model has to be field wired Higher amperage mPDUs offer more outlets allow more equipment to be connected and are especially suited to the high density server deployments Small Form Factor and Flexible Mounting Options The Control Unit is zero U or 1U rack mountable And the Extensi...

Page 3: ... out devices Current Ratings from 16A to 40A Modular PDUs are available in a wide range including four high volt models ranging from 16A to 40A current ratings and one low voltage 24A model Compatibility Ideal for use with the HP 9000 and 10000 Series Racks the Modular PDUs are largely designed for the dense rack environment These Modular PDUs connect directly to the facility input power In additi...

Page 4: ...o 60 C Storage Relative Humidity 5 to 95 Storage Elevation 0 to 30 000 ft 0 to 9144 m Conformance Standards UL CUL CE NOM D 16A and 40A models UL CUL NOM 24A High and Low voltage models CE D 32A model Kit Contents 24 40A Modular PDUs ship with x1 Control Unit and x4 Extension Bars 16A Modular PDU ship with x1 Control Unit and x2 Extension Bars All models ship with 0U 1U Mounting brackets hardware ...

Page 5: ...ea Input 3 6m attached cable with L6 30P Output Four IEC320 C19 12A ea Input 3 6m attached cable with IEC309 32A Output Four IEC320 C19 12A ea Input Hardwire Output Four IEC320 C19 12A ea Note Manual ON Off control provided for each load group switch guards provided to prevent inadvertent power Off The Control unit for the 16A model has 2 outputs while the Control Unit for all other Modular PDUs h...

Page 6: ...Bars while all other 24 40A models ship with 4 Extension Bars 32 IEC 320 C 13 32 IEC 320 C 13 24 IEC 320 C 13 4 IEC 320 C 19 Applications Connects to low voltage models of the UPS R3000 XR and may also be connected directly into the facility input Connects to the high voltage models of the UPS R3000 XR and R6000 Note Except for the UPS R3000 XR North America high volt model where an additional cab...

Page 7: ...uired on the PDU for connecting the RILOE cards Please refer to the Power Cord Matrix for more information on power cords cable part numbers input output descriptions ftp ftp compaq com pub products servers proliantstorage power protection powercordmatrix pdf 2002 Hewlett Packard Company Hewlett Packard the Hewlett Packard logo CarePaq ProLiant and StorageWorks are trademarks of Hewlett Packard Co...

Reviews: