Connecting the ground bonding 

cable 

  

 

NOTE:

  This section is only applicable if a control unit was 

shipped as part of your kit. 

  

The ground bonding screw is provided as an attachment point for 
conductors. Use a ground bonding cable if the rack contains any 

conductors for the purpose of functional grounding or bonding of 

ungrounded metal parts. 

The ground bonding cable is not included in this kit. 

 

 

Connecting the 16-A modular PDU 

(model 252663-B24 WW) to the 

power source 

 

 

Hardwiring the 40-A modular PDU 

The 40-A modular PDU (model 252663-B21 WW) must be 

hardwired by a qualified electrician in accordance with local 
electrical installation codes. 

 

Connecting devices 

When connecting devices, distribute the loads evenly to remain 

within the capability of the extension bars and control unit. 

     

Control 

unit 

Total rating of 

control unit 

Outlet 

style 

Load 

CB 

rating 

Individual 

outlet 

rating 

228481-

001 

24 A 

IEC 320-

C19 

15 A 

12 A 

228481-
002 

24 A 

IEC 320-
C19 

15 A 

12 A 

228481-
003 

32 A 

IEC 320-
C19 

15 A 

12 A 

228481-
004 

40 A 

IEC 320-
C19 

15 A 

12 A 

228481-

006 

16 A 

IEC 320-

C19 

10 A 

8 A 

228481-

007 

40 A 

IEC 320-

C19 

15 A 

12 A 

228481-
008 

40 A 

IEC 320-
C19 

15 A 

12 A 

435530-
001 

41.6 A 

IEC 320-
C19 

20 A 

16 A 

435530-
003 

48 A 

IEC 320-
C19 

16 A 

16 A 

458745-

001 

83.13 A 

IEC 309-

C19 

20 A 

16 A 

481337-

001 

96 A 

IEC 309-

C19 

16 A 

16 A 

484168-
001 

40 A 

IEC 320-
C19 

20 A 

16 A 

 

     

Extension 
bar 

Total rating of 
extension bar 

Outlet 
style 

Individual outlet 
rating 

411273-

001 

16 A 

NEMA 5-

15R 

12 A 

411273-
002 

16 A 

IEC 320-
C13 

10 A 

228480-
003 

12 A 

IEC 320-
C19 

12 A 

 

 

Checking the circuit breakers 

If power to a device is interrupted, check the circuit breakers and 
reset if necessary. If power is still not restored, contact your HP 

authorized service representative. 

Summary of Contents for 252663-B24 - PDU Power Distribution Strip

Page 1: ...ts circuit breakers move to Off position minimizing downtime Power cord retention Recessed handles to prevent inadvertent power off The extension bars if included provide the following features Multiple power outlets conveniently located for quick and easy equipment power connections Lighted main power indicator Attached 2 m 6 ft input power cords Power cord retention and power cord labeling Modul...

Page 2: ...ceed the total output rating marked on the mPDU WARNING To reduce the risk of personal injury from high leakage current verify earth connection before connecting the power supply The summation of input power for multiple pieces of information technology equipment through the use of power products can result in high leakage currents If the total system leakage current for a system of components exc...

Page 3: ...TL 4 8 4 40 6 252663 D74 NA JPN 0 0 0 6 252663 B33 INTL 0 0 0 6 252663 D75 NA JPN 0 0 0 6 252663 B34 INTL 0 0 0 6 AF500A 2 4 2 40 0 AF501A 2 4 2 40 0 AF511A 0 0 0 6 Model Number of extension bars Number of single double brackets Number of extension bar power cord retention bands Number of control unit tie wraps AF512A 0 0 0 6 AF513A 0 0 0 6 AF518A 0 0 0 6 AF519A 0 0 0 6 Required tools The followin...

Page 4: ...Installing the 0U brackets Installing the 1U brackets ...

Page 5: ... the rack when installing in a square holed rail Installing the control unit in a square and round holed rail NOTE Use the sheet metal mounting screws that are included with this kit when installing in a square and round holed rail Installing the extension bars if included The cord retention brackets are shown for clarification in the following diagrams though installation of the cord retention br...

Page 6: ...Installing the extension bars using single stick mounting brackets Connecting and securing the power cords ...

Page 7: ...n bars and control unit Control unit Total rating of control unit Outlet style Load CB rating Individual outlet rating 228481 001 24 A IEC 320 C19 15 A 12 A 228481 002 24 A IEC 320 C19 15 A 12 A 228481 003 32 A IEC 320 C19 15 A 12 A 228481 004 40 A IEC 320 C19 15 A 12 A 228481 006 16 A IEC 320 C19 10 A 8 A 228481 007 40 A IEC 320 C19 15 A 12 A 228481 008 40 A IEC 320 C19 15 A 12 A 435530 001 41 6 ...

Page 8: ......

Reviews: