Communication 76
Pin number Signal name Function
Direction from the UPS
4
—
No connection
—
5
GND
Signal common (tied to chassis)
—
6
—
No connection
—
7
—
No connection
—
8
—
No connection
—
9
—
No connection
—
Control terminals
The cables should be connected to the control terminal with a mating connector. Input and output terminals
have a functional isolation from terminal to terminal. They are connected to the UPS chassis through
individual 1 M
W
resistors.
If using a semiconductor switch type, pay attention to the proper polarity. A relay or other mechanical control
is preferred.
Relay output contacts
WARNING:
The relay output contacts must not be connected to any utility connected circuits.
Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of
30 VAC/1 A and 60 Vdc/2 A nominal values.