Troubleshooting 99
Remove one or more load devices to reduce the power requirements.
Selective trip
Possible cause:
The UPS detected an internal fault.
Action
: If the condition persists, contact an HP authorized service representative.
Site wiring condition
Action
: Contact a qualified electrician to be sure that:
•
The line and neutral wires are not reversed in the wall outlet.
•
A ground wire connection does not exist.
UPS detects software incompatibility
Possible cause:
The UPS detects a paralleled UPS with a later firmware version. Mixing major firmware
versions is not supported. For minor software versions, the alarm does not prevent operation, but different
firmware versions in a parallel system cause conflicts.
Action:
Verify that all UPSs in the parallel system have the same firmware version. To update the firmware,
see "Updating the UPS firmware (on page
)."
UPS does not power down
Possible cause:
The batteries or electronics module is being replaced.
Action:
1.
Complete the replacement procedure.
2.
Power down the UPS.
o
Standalone UPS configuration—See "Powering down the standalone UPS (on page
)."
o
Individual UPS in a parallel configuration—See "Powering down an individual paralleled UPS (on
page
)."
o
Parallel UPS configuration—See "Powering down the parallel system (on page
)."
UPS does not power up
Action
:
1.
Be sure the main utility circuit breaker is in the On position.
2.
Check the power source at the utility power receptacle.
3.
Be sure that the normally-closed REPO is closed, and that the normally-open REPO is open.
4.
If replacing the batteries or electronics module, complete the procedure before powering up the UPS.
5.
Power up the UPS.
o
Standalone UPS configuration—See "Powering up the standalone UPS (on page
)."