background image

Page 18 

 

Installer’s Information Manual 

SECTION 9.  INSTALLING DUCT 
SYSTEM 

Properly size duct system based on heat loss and heat gain 
calculations to ensure good heating and cooling 
installations, potentially fewer call-backs, and delivery of 
required circulating air.  Install duct system to meet current 
Standard for Installations of Warm Air Heating and Air 
Systems ASHRAE/NFPA 90 and local codes. 

CAUTION: Failure to follow these standards could reduce 
airflow or increase air leakage, resulting in reduced system 
performance or fu rnace damage. 

Design duct system so fu rnace will operate at a static 
pressure of 0.50 inches W.C. or less.  This static pressure 
limitation includes the total pressure losses on both supply 
air side and retu rn air side of system.  Supply side pressure 
loss includes cooling coil, ducts and room registers.  Return 
side pressure loss includes retu rn grilles and ducts.  
Pressure losses are calculated based on 400 CFM per ton 
of cooling. 

SUPPLY AIR DUCT WORK 

Supply air duct (plenum) connections must be at least as 
big as fu rnace supply opening.  Seal supply-air ductwork to 
furnace casing, walls, ceilings or floors it passes through.  
End ductwork outside fu rnace space. 

On furnaces not equipped with a cooling coil, a removable 
access panel that is large enough to allow viewing of the 
heat exchanger should be provided in the supply duct.  The 
access panel should be accessible when the fu rnace is 
installed.  Seal access-panel cover to prevent leaks. 

RETURN AIR DUCT WORK 

When furnace is installed so that supply air ducts carry air 
to areas outside the space containing the fu rnace, return air 
must be handled by a duct(s) sealed to fu rnace casing and 
terminating outside the space containing fu rnace. 

 

 

WARNING

: Failure to seal retu rn-air  ductwork 

could allow combustion products to enter circulating air 
stream resulting in injury or death by asphyxiation. 

Air delivery above 1800 CFM requires that both sides of 
furnace be used for retu rn air, or a combination of one side 
and bottom or bottom only.  

If bottom return air is not used, you must attach a solid 
bottom-closure panel to bottom retu rn-air opening.  Bottom 
closure panel is available from manufacturer.  See Table 5 
for bottom closure part numbers. 

Table 5.  Bottom Closure Part Numbers. 

GAS 

INPUT* 

(Btu/hr) 

MOTOR* 

HORSE- 
POWER 

BOTTOM CLOSURE 

PART NUMBER 

54,000 

1/3 

4045901 

72,000 
90,000 

1/2 

 

4045901 

72,000 
90,000 

3/4 

4045902 

108,000 
126,000 

3/4 

4045903 

* GAS INPUT and MOTOR HP can be found on furnace 
rating plate. 

 

 

WARNING

: Failure to install bottom closure panel 

could allow combustion products to enter circulating air 
stream, resulting in injury or death by asphyxiation. 

DUCT DAMPERS 

You may balance  airflow with dampers installed in each 
branch run duct and adjust for even temperature throughout 
the heated space.  For proper fu rnace operation, make sure 
of the following: 

??

Supply air registers and retu rn air grilles are open; 

??

Rugs, carpets, drapes or fu rniture are clear of registers 
and grilles; 

??

Size and shape of supply air plenum is correct; 

??

Number of supply air ducts is correct. 

LOCATION OF COOLING COIL 

If furnace will share common duct system with a separate 
cooling unit, install fu rnace parallel to or upstream of 
cooling unit.  This avoids condensation in heating element.  
Do not install cooling coil in retu rn-air  ductwork.  With 
parallel flow, dampers must be installed to prevent chilled 
air from entering fu rnace.  If dampers are not in full heat or 
full cool position, fu rnace or cooling unit must not operate. 

SECTION 10.  SELECTING AND 
INSTALLING FILTER CABINETS 

Properly installed air filters keep blower motor, blower 
wheel and cooling coil (if installed) clean.  Filters and filter 
cabinets are not supplied with this fu rnace.  Filters and filter 
cabinets must be field supplied or obtained from the 
manufacturer.  The manufacturer has bottom and side filter 
cabinets available.  This fu rnace was designed for an 
external filter(s).  Do not install air filters inside fu rnace 
casing.  Obtain and install proper filter frames and correctly 
sized filters.  To inspect, clean or replace air filters, follow 
the instructions in the User’s Information Manual. 

CAUTION: You must install air filters to keep blower motor, 
blower wheel and cooling coil (if installed) clean.  Dirty 
equipment may reduce system efficiency or cause erratic 
control performance and can result in damage to blower 
motor, heat exchanger or air conditioner (if installed). 

Summary of Contents for 422690

Page 1: ... give you the documents listed on opposite side You should immediately read the User s Information Manual for important safety information to keep y ou and your family safe Keep these as long as you keep your furnace Pass them on to future furnace purchasers or users If any of the documents are missing or illegible contact your installer or furnace manufacturer for replacement Throughout this manu...

Page 2: ... in this manual Must is mandatory Should is advisory WARNING Read and follow the safety rules in this section and throughout this manual Failure to do so could cause improper furnace operation resulting in damage injury or death Rule 1 Use only gas approved for use in this furnace as indicated on furnace rating plate Use only natural gas in furnaces designed for natural gas Use only propane LP gas...

Page 3: ...clearance for service WARNING Some insulating materials are combustible When a furnace is installed in an attic or other insulated space keep all insulating materials at least 12 inches away from furnace and combustion air inlet Failure to do so could cause a fire You may install furnace on non combustible flooring or on wood flooring WARNING Do not install furnace on carpeting tile or other combu...

Page 4: ...0 2 0 2 OR 3 90 000 1 2 17 1 2 15 3 4 15 15 16 1 0 0 2 0 2 OR 3 90 000 3 4 20 1 2 18 3 4 18 15 16 1 0 0 2 0 2 OR 3 108 000 3 4 23 1 2 21 3 4 21 15 16 1 0 0 2 0 3 126 000 3 4 23 1 2 21 3 4 21 15 16 1 0 0 2 0 3 See Furnace Rating Plate located on blower door These are furnace dimensions See Sections 9 and 10 for proper ductwork and floor opening dimensions Certified for installation on wood flooring...

Page 5: ...gs that may hold water Support horizontal portions of vent pipe every 5 feet 3 feet for SDR 21 or SDR 26 pipe Protect vent from freezing Long runs of vent pipe installed in an unconditioned space may require insulation to prevent freezing of condensate Furnace can be vented from either left or right side See Figure 2 As shipped furnace is setup for venting through the left side Right side venting ...

Page 6: ...peration while any other appliances connected to the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 Installation Codes Determine that there is no blockage or restriction leakage corrosion and other deficiencies whi...

Page 7: ...126 000 Btu hr model may need a high altitude pressure switch when installed at elevations between 3000 and 4000 feet Above 4000 feet this model requires a high altitude switch for all installations All furnace models require the high altitude pressure switch when installed at elevations above 6000 feet The high altitude pressure switch is supplied with the LP Conversion Kit 4226000 and the Natura...

Page 8: ...0 15 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 21 18 14 11 72 000 3 40 40 40 40 40 40 40 40 5001 6000 90 000 3 40 40 40 40 40 40 40 40 108 000 3 40 35 30 25 20 15 10 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 40 40 40 40 36 32 28 2...

Page 9: ... Attach a combustion air pipe to combustion air inlet collar on top of furnace Use rubber coupling and hose clamps supplied with furnace See Figure 5 Figure 5 Combustion Air Pipe Connection to Furnace for Direct Vent NON DIRECT VENTING INSTRUCTIONS one pipe system DETERMINING VENT LENGTH See Table 2 for maximum vent pipe length Include any termination elbows when determining maximum allowable vent...

Page 10: ... 60 55 50 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 62 57 52 47 42 37 32 27 54 000 2 43 40 37 33 30 27 24 20 72 000 2 21 18 14 11 72 000 3 150 150 150 150 150 150 150 150 5001 6000 90 000 3 70 65 60 55 50 45 40 35 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 62 57 52 47 42 37 32 27 54 000 2 110 106 104 100 96 92 88 84 72 000 2 50 46 43 40 36 32 29 25 72 000 3 150 150 150 150...

Page 11: ...requirements of all gas appliances in the building You must also allow for reduction of air available for combustion and ventilation caused by exhaust fans range hoods and fireplaces Sufficient air must be provided to ensure there will not be a negative pressure in furnace room or space In addition there must be a positive seal between furnace and return air duct to avoid pulling air from burner a...

Page 12: ...om an unconfined space within the building or from outdoors However if the building is of unusually tight construction all combustion air must come from outdoors Also if returnair is taken directly from a hallway or space next to furnace that communicates with furnace spaces all combustion air must come from outdoors WARNING You must provide permanent air openings to a confined furnace installatio...

Page 13: ...0 108 000 27 6 113 000 126 000 31 5 7 153 000 144 000 36 7 153 000 When communicating with the outdoors through vertical ducts openings and ducts must have a minimum free area of one square inch per 4 000 Btu per hour of total combined input rating of all gas appliances within furnace space See Figure 11 and Table 3 Figure 11 All Air Through Vertical Ducts From Spaces That Freely Access The Outdoo...

Page 14: ...piping is large enough for all appliances connected to it to operate at once without lowering gas supply pressure Failure to do so could cause lighting or burning problems on any of the appliances Always use a pipe thread compound that is resistant to propane LP gas solvent action Sparingly apply thread compound to all joints on male threads only starting two threads from the end INSTALLATION Gas ...

Page 15: ...cal Code CSA C22 1 WARNING Failure to provide a proper electrical ground could result in electric shock or fire Provide furnace with its own separate electrical circuit and means of circuit protection Furnace must have an electrical disconnect switch located at furnace WARNING Failure to provide the above shut off means could result in electrical shock or fire Use electrical wiring that meets curr...

Page 16: ...Page 16 Installer s Information Manual Figure 15 Furnace Wiring Diagram ...

Page 17: ... is de energized Main blower remains energized for 60 seconds CONSTANT FAN MODE Thermostat calls for constant fan R and G terminals connected Fan Timer energizes main blower on heating speed A call for cooling mode while in constant fan mode causes main blower to change from heating to cooling speed Sixty seconds after the call for cooling mode ends main blower changes back to heating speed A call...

Page 18: ...o bottom return air opening Bottom closure panel is available from manufacturer See Table 5 for bottom closure part numbers Table 5 Bottom Closure Part Numbers GAS INPUT Btu hr MOTOR HORSE POWER BOTTOM CLOSURE PART NUMBER 54 000 1 3 4045901 72 000 90 000 1 2 4045901 72 000 90 000 3 4 4045902 108 000 126 000 3 4 4045903 GAS INPUT and MOTOR HP can be found on furnace rating plate WARNING Failure to ...

Page 19: ...25 X 1 72 000 90 000 108 000 126 000 3 4 20 X 25 X 1 20 X 25 X 1 GAS INPUT and MOTOR HP can be found on furnace rating plate FILTER CABINETS Use a bottom filter cabinet side filter cabinet or return air filter grille Field fabricated filter cabinets should allow 1 inch spacing between filter and furnace Placing a field supplied filter directly against furnace bottom or side will decrease airflow a...

Page 20: ...lowly open equipment shut off valve in gas supply line just ahead of furnace 7 Slowly open 1 8 NPT manual shut off valve leading to manometer 8 Turn on all gas appliances attached to gas supply line 9 With furnace operating read gas supply pressure on manometer Natural gas supply pressure must be between 5 and 7 inches W C Propane gas LP supply pressure must be between 11 and 13 inches W C 10 If g...

Page 21: ...place burner access panel using three screws removed in step 2 SECTION 14 CHECKING GAS INPUT RATE It is the installer s responsibility to see that the Btu input rate of the furnace is properly adjusted Under firing could cause inadequate heat primary heat exchanger corrosion and or ignition problems Over firing could cause sooting flame impingement and or overheating of heat exchanger WARNING Fail...

Page 22: ...ustment 3 Start furnace following Operating Instructions on front door 4 Let furnace warm up for 6 minutes 5 Adjust manifold pressure to 10 0 inches W C 0 3 inches W C See Section 13 Manifold Pressure Adjustment WARNING Do not set Propane LP manifold pressure at 11 0 inches W C It could cause heat exchanger failure NOTE NOx reducing screens must be removed from each tube of California NOx furnaces...

Page 23: ...al power and gas before changing orifices Follow this procedure 1 Turn off electricity at electrical disconnect switch next to furnace 2 Turn off equipment shut off valve in gas supply line just ahead of furnace 3 Remove three screws holding burner access panel in place Remove burner access panel 4 Starting with burner farthest from gas control remove main burner screws and main burners Note how b...

Page 24: ...0 1 2 35 65 ML YEL 72 000 3 4 30 60 ML YEL 90 000 1 2 45 75 MH BLUE 90 000 3 4 35 65 MH BLUE 108 000 3 4 35 65 MH BLUE 126 000 3 4 45 75 MH BLUE Gas Input and Motor HP can be found on rating plate These are factory settings Table 10 Cooling Speed Selection GAS MOTOR AIR CONDITIONING TONNAGE INPUT SIZE AT 0 5 INCHES WC Btu hr HP 1 5 2 2 5 3 3 5 4 5 54 000 1 3 LO ML MH HI 72 000 1 2 LO ML HI 72 000 ...

Page 25: ...should be set according to Table 9 Cooling speed should be set to meet cooling equipment requirements See Table 10 for cooling airflow capacities at 0 5 inch W C 6 Place one thermometer in supply air plenum approximately 2 feet from furnace Locate thermometer tip in center of plenum to ensure proper temperature measurement 7 Place second thermometer in return air duct approximately 2 feet from fur...

Page 26: ...itches located near 24 volt terminal strip on Fan Timer 2 Determine switch settings for desired heating blower off delay See Figure 23 3 Set switches on Fan Timer using a small screwdriver NOTE Cooling blower off delay is fixed at 60 seconds and is not adjustable Figure 23 Heating Blower Off Delay SECTION 23 MAINTAINING FURNACE IN GOOD WORKING ORDER WARNING Use replacement parts listed in parts li...

Page 27: ...Industries name Choose from the T87 round w subbase T834 heating and cooling or the T8699 Chronotherm III available in white only PROPANE CONVERSION KIT BELOW 6 000 ft Includes propane regulator spring kit propane pilot orifice and main burner orifices HIGH ALTITUDE PROPANE CONVERSION KIT ABOVE 6 000 ft Includes propane regulator spring kit propane pilot orifice main burner orifices and high altit...

Reviews: