Capacity (in watts)
UPS Model
4500
R5500
12000
R12000
Table 23 UPS operating time limits
Minutes of operation
Load (percent)
With 2 ERMs
With 1 ERM
With standby battery
R1500
49
23
5
100
63
32
6
80
161
57
13
50
290
146
34
20
R3000
20
5
100
30
6.5
80
45
12
50
120
40
20
R5500
46
24
7
100
60
31
9
80
106
61
19
50
303
169
59
20
R12000
18
11
5
100
24
15
7
80
41
28
14
50
101
69
43
20
Table 24 EVA8400 UPS loading
% of UPS capacity
Watts
Enclosures
R12000
R5500
41.0
4920
12
Non-standard rack specifications