Preface-iv
LEAKAGE CURRENT:
WARNING
Due to the types of products able to be installed in this product there
is a risk of high leakage current (>3.5 mA). Reliable ground circuit
continuity is vital for safe operation of this product. To reduce the
risk of electric shock, earth connection is essential before connecting
the supply. Never operate product with the ground conductor
disconnected.
POWER LIMITATIONS:
WARNING
IMPORTANT SAFETY NOTE FOR INSTALLATION
For installing cabinets containing switchless Power Distribution
Units (PDU part numbers C2785-63004, C2786-63008, C2786-63009 or
C2786-63010):
The socket outlet shall be installed near the rack cabinet and shall
be easily accessible, because the plug on the power supply cord is
intended to serve as the disconnect device for this cabinet.
The Total output current rating of the PDU equals the output
current rating of the UPS receptacle to which the PDU is connected
(up to 16 Amps maximum). Check the total input current ratings of
the equipment installed in the cabinet to avoid overloading the UPS.
WARNING
IMPORTANT SAFETY NOTE FOR INSTALLATION
For installing dual-voltage-range-rated Power Distribution Units
(PDU part numbers C2785-63004 or C2786-63008) for connection to an
Uniterruptable Power Supply (UPS):
The voltage of the PDU receptacles equals the voltage of the UPS
receptacle to which the PDU is connected (200-240V range). CHECK
THE UPS OUTPUT VOLTAGE BEFORE CONNECTING ANY
EUIPMENT TO THE PDU! Failure to check the voltage could lead to
severe equipment damage.
CAUTION
To reduce the risk of overload, do not load any single PDU with more than a
maximum of 16 Amperes. In addition, do not load a single NEMA 5-15
receptacle with more than 15 Amperes and any single IEC 320 receptacle
with more than 10 Amperes.
ACCESSORIES:
CAUTION
This product has been designed to be used with specific electrical accessories
(i.e. PDU's). The use of any other accessory is not recommended or supported.
Summary of Contents for A3764A
Page 4: ...iv Contents ...
Page 6: ...vi Figures ...
Page 7: ...Tables vii Table 4 1 A3764A and A3765A Cabinet Replaceable Parts 4 4 ...
Page 8: ...viii Tables ...
Page 10: ...Preface ii ...
Page 14: ...Preface vi ...
Page 18: ...1 4 Chapter1 Introduction Installation Site Requirements ...
Page 28: ...2 10 Chapter2 Unpacking and Installation Repackaging the Cabinet for Shipment ...
Page 32: ...3 4 Chapter3 Cabinet Operation Turning Off the Computer System With UPS ...
Page 34: ...4 2 Chapter4 Removal and Replacement Procedures Figure 4 1 Cabinet Exploded View Front ...
Page 35: ...Chapter 4 4 3 Removal and Replacement Procedures Figure 4 2 Cabinet Exploded View Back ...
Page 56: ...4 24 Chapter4 Removal and Replacement Procedures Removal and Replacement Procedures ...
Page 59: ...Chapter 5 5 3 Computer Access Button up Procedures ...
Page 60: ...5 4 Chapter5 Computer Access Button up Procedures ...