Chapter 5
Troubleshooting
69
To view the controller enclosure’s temperature status, in SMU, as an Advanced
Manage user:
●
Select Monitor > Status > Advanced Settings > Temperature Status.
Power-and-Cooling Module Voltage Sensors
Power supply voltage sensors ensure that an enclosure’s power supply voltage is
within normal ranges. There are three voltage sensors per power-and-cooling
module.
Table 5-5
Voltage Sensor Descriptions
Sensor
Event/Fault ID LED Condition
Power Supply 1 Voltage, 12V
< 11.00V
> 13.00V
Power Supply 1 Voltage, 5V
< 4.00V
> 6.00V
Power Supply 1 Voltage, 3.3V
< 3.00V
> 3.80V