3.
Connect the HPE Adaptive Rack Cooling System to the pickups in the IT racks with flexible tubing.
When facing the HPE Adaptive Rack Cooling System from the front (fans showing), the pressure
reference ports are located in the upper-left side of the control box at the top of the HPE Adaptive
Rack Cooling System.
• Connect Port 1 (DP1—left port) to the rack on the left side of the HPE Adaptive Rack Cooling
System.
• Connect Port 2 (DP2—right port) to the rack on the right side of the HPE Adaptive Rack Cooling
System.
4.
Secure the tubing between the port on the HPE Adaptive Rack Cooling System and the final
connection in the IT rack.
5.
Mount the rear HPE Adaptive Rack Cooling System pressure pickup tube with the hose barb facing
right.
24
Configuration