CAUTION:
This equipment is designed to permit the connection of the earthed conductor of the DC supply
circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
• This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply
system earthing electrode conductor is connected.
• This equipment must be located in the same immediate area (such as adjacent cabinets) as any
other equipment that has a connection between the earthed conductor of the same DC supply
circuit and the earthing conductor, and also the point of earthing of the DC system. The DC
system must be earthed elsewhere.
• The DC supply source is to be located within the same premises as the equipment.
• Switching or disconnecting devices must not be in the earthed circuit conductor between the DC
source and the point of connection of the earthing electrode conductor.
HPE 800W Flex Slot Titanium Hot Plug Low Halogen Power Supply
Specification
Value
Input requirements
Rated input voltage
200 VAC to 240 VAC
240 VDC for China only
Rated input frequency
50 Hz to 60 Hz
Not applicable to 240 VDC
Rated input current
4.35 A at 200 VAC 3.62 A at 240 VAC
3.62 A at 240 VDC for China only
Maximum rated input power
851 W at 200 VAC
848 W at 240 VAC
848 W at 240 VDC for China only
BTUs per hour
2,905 at 200 VAC
2,969 at 240 VAC
2,969 at 240 VDC for China only
Power supply output
Rated steady-state power
800 W at 200 VAC to 240 VAC input
800 W at 240 VDC input for China only
Maximum peak power
800 W at 200 VAC to 240 VAC input
800 W at 240 VDC input for China only
HPE 800W Flex Slot Titanium Hot Plug Low Halogen Power Supply
71