Ground Bonding kit 67
Installing the ground bonding rack option kit on HP 10000 Series
Rack side panels
From the system chassis rail to the side panel:
1.
Connect a 36.83-cm (14.5-in) and a 15.24-cm (6-in) grounding strap with connectors together.
2.
Insert a T-25 Torx screw through the end of the 36.83-cm (14.5-in) grounding strap, and secure it to the
system chassis rail.
3.
Place the end of the 15.24-cm (6-in) grounding strap over the grounding lug on the side panel.
4.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the side panel
and tighten.
5.
Repeat steps 1 through 4 for the other side panel.
Installing the ground bonding rack option kit on HP 10000 Series
Rack fan kits
From the grounding lug on the rack top to the grounding lug on the fan kit:
1.
Place one end of a 15.24-cm (6-in) grounding strap over the grounding lug on the rack top.
2.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the rack top
and tighten.
3.
Place the other end of the same grounding strap over the grounding lug on the perforated panel.