Connecting and configuring optional hardware
Hardware overview
HPE G2 Series Metered, Switched, and Metered & Switched Power Distribution Units monitor environmental
conditions of a rack with the addition of HPE optional environmental sensors. Conditions such as
temperature, humidity, leak detection, and intrusion can be monitored with the sensors. These conditions are
all vital aspects of maintaining an efficiently performing data center. Users and administrators can monitor the
status and view reports and alarms of specific conditions in and around a PDU or server rack.
The following environmental sensors are available:
• Temperature sensor
• Temperature and humidity sensor
• 3-tempe 1-humidity sensor
• Open/Close door sensor
• Leak detection sensor
• Sensor port hub
• Leak detection sensor extension
Sensor
SKU
Description
Sensor
Measurement
Temperature sensor
P9T00A
Monitors the temperature in the rack.
1
Temperature and
humidity sensor
P9T01A
Monitors the temperature and relative humidity
in the rack.
2
3-tempe 1-
humidity sensor
P9T02A
Monitors the temperature in three areas using
three separate probes, and the relative humidity
using one probe.
4
Open/Close door sensor
P9T03A
Sends an alarm or notification when a door on
which the sensor is installed has been opened
more than 10 mm. This kit includes two door
contacts (one for the front and one for the rear
door).
2
Rope fluid leak sensor
P9T04A
Monitors for early detection of liquid with a
resistivity of less than 2M Ohms (including
distilled water) in the monitored area. The kit
includes a 6m rope, and optional additional rope
can be added (see P9T08A).
1
Sensor port hub
P9T07A
Allows for up to three environmental sensors to
be connected to the PDU.
N/A
Leak detection sensor
extension
P9T08A
The kit includes one additional 6m length rope
to pair with the leak detection sensor (P9T03A).
A total of four extensions can be added to the
leak detection sensor for a total length of 30m.
N/A
The optional environmental sensors can be installed before or after completing the PDU installation or startup,
and can be installed without turning off power to the PDU or the devices connected. HPE G2 Series Metered,
110
Connecting and configuring optional hardware
Summary of Contents for HPE G2 Series
Page 16: ...3 Secure the tie wrap 16 Introduction ...
Page 20: ...20 Introduction ...
Page 23: ...Installing the PDU 23 ...
Page 25: ... Outlets facing the back of the rack Installing the PDU 25 ...
Page 26: ... Outlets facing the front of the rack 26 Installing the PDU ...
Page 28: ... Two mid height PDUs with outlets facing towards the center of the rack 28 Installing the PDU ...
Page 31: ... Half height Installing the PDU 31 ...
Page 35: ...Installing the PDU 35 ...
Page 37: ...2 Install the PDU in the rack frame Installing the PDU 37 ...
Page 47: ...3 Install the PDU Installing the PDU 47 ...
Page 49: ...Installing the PDU 49 ...
Page 64: ...Web menu options Menu Illustration Overview Alarms 64 Remote configuration ...
Page 65: ...Menu Illustration Help Table Continued Remote configuration 65 ...
Page 66: ...Menu Illustration Language 66 Remote configuration ...
Page 67: ...Menu Illustration Logs Remote configuration 67 ...
Page 68: ...Menu Illustration Settings 68 Remote configuration ...
Page 84: ...84 Remote configuration ...
Page 92: ...92 Configuring local access ...
Page 99: ...Local display 99 ...
Page 101: ...Local display 101 ...
Page 107: ...Local display 107 ...
Page 120: ...120 Connecting and configuring optional hardware ...