Installation Manual
CA294-03070 rev 00
page 73 of 153
WARNING:
All electrical power connections to the chiller must
be performed only by a local authorized and
licensed electrician.
1.
Install the chiller. Refer to the
UltraFilter ultracool 0400 installation guide
.
Make sure that the external filter supplied by the chiller supplier is installed. The filter should
be installed at the chiller return pipe.
NOTE:
Do not open any main water valves until the water hose
connections between the chiller, printing engines, and ink
cabinets are verified as correct.
Figure 53 Chiller pipe routing (Europe)
Chiller
External Drainage Tank
Engine No. 2
Blower
Engine No. 1
Blower
160 cm
(63 inches)
External wall
2" pipe
Flow-rate
gauge
Temperature
gauge
2" main ball
valve
1" ball valve
Barb fitting,
1" inside
diameter
1" flexible
tube installed
by HP
1" pipe
2" ball valve. Closed
during normal press
operation. Open for
chiller maintenance
and inspection.
2" one-way valve suitable for 100
liter/minute flow rate with
minimum pressure drop. Present
when chiller water exit is below
press level.