Table 5 HP P10000 3PAR Storage System Power Requirements per Cabinet
(continued)
200
200
Drive Chassis (no magazines)
Drive Magazine
3
4 x 100 GB SSD Drive Magazine
5.5
9.8
Watts
19
33
BTUs/hour
4 x 200 GB SSD Drive Magazine
7
10.3
Watts
24
35
BTUs/hour
4 x 300 GB FC Drive Magazine
57
75
Watts
195
256
BTUs/hour
4 x 600 GB FC Drive Magazine
65
76
Watts
222
258
BTUs/hour
4 x 2 TB NL Drive Magazine
38
62
Watts
131
211
BTUs/hour
Service Processor
317
Watts
1,082 BTUs/hr.
BTUs/hour (fully populated)
1
Theoretical maximum based on branch circuit capacity.
2
Under maximum load.
3
Up to 10 drive magazines (40 drives) per drive chassis.
NOTE:
Refer to
“Power Requirements” (page 29)
for complete details.
Environmental Specifications
The following table lists the environmental specifications for the HP P10000 3PAR Storage Systems.
Table 6 Environmental Specifications for the HP P10000 3PAR Storage System
Value
Specification
0 –10,000 ft (3,048 m) 0 –40,000 ft (12,192 m)
Altitude Operating Nonoperating
50 –104° F (10–40° C) 0–3,000 ft (914.4 m) 50 –95° F
(10 –35° C) 3,000–10,000 ft (914–3,048 m) –40 –203°
F (–40– 95° C) 0–40,000 ft (0–12,192 m)
Ambient temperature Operating Nonoperating
18° F/hr (10° C/hr) 18° F/hr (10° C/hr)
Temperature gradient Operating Nonoperating
20 – 80 percent noncondensing, maximum gradient 10
percent per hour
Relative humidity
12
System Components and Specifications
Summary of Contents for P10000
Page 30: ...Figure 12 Power Supplies Within the Power Domains 30 Power Requirements ...
Page 59: ...French battery notice German battery notice Battery replacement notices 59 ...
Page 60: ...Italian battery notice Japanese battery notice 60 Regulatory compliance notices ...
Page 61: ...Spanish battery notice Battery replacement notices 61 ...