room upgrades for high heat loads. It is based on Liebert's TeleCool product, which has been installed in
600 telecommunications equipment rooms throughout the world. The system utilizes heat exchanger
pump units to distribute fluid in a closed system through patented cooling coils throughout the data
center. The overhead cooling coils are highly efficient heat exchangers with blowers that direct the
cooling where required. The blowers are adjustable to allow flexibility for changing equipment
placement or room configurations. Equipment is protected from possible leaks in the cooling coils by the
patented monitoring system and purge function that detects any leak and safely purges all fluid from the
affected coils. DataCool has interleaved cooling coils to enable the system to withstand a single point of
failure and maintain cooling capability.
Features and Benefits
Features and Benefits
Features and Benefits
Features and Benefits
Fully distributed cooling with localized distribution
Even cooling over long distances
High heat load cooling capacity (up to 500 W per square foot)
Meets demand for narrow operating temperature for computing systems
Allows computer equipment upgrade for existing floor cooled data rooms
Floor space savings from removal of centralized air distribution
Withstand single point of failures
For More Information
For More Information
For More Information
For More Information
http://www.liebert.com/assets/products/english/products/env/datacool/60hz/bro_8pg/
acrobat/sl_16700.pdf
HP has entered into an agreement with Liebert to reference sell the DataCool solution.
The HP/Liebert business relationship will be managed by HP Complementary Products Division.
DataCool will be reference by HP. Installation, service and support will be performed by Liebert.
HP will compensate the HP Sales Representative and District Manager for each DataCool that
Liebert sells to a customer referred by HP.
An HP/Liebert DataCool website will be setup to get more information on the product and to
manage the reference sales process. Please go to
http://hpcp.grenoble.hp.com/
for more
information.
Environmental
Environmental
Environmental
Environmental
20-30 degrees C inlet ambient temperature
0-10,000 feet
2600 CFM with N+1 blowers. 2250 CFM with N.
65 dBA noise level
Uninterruptible Power
Uninterruptible Power
Uninterruptible Power
Uninterruptible Power
Supplies (UPS)
Supplies (UPS)
Supplies (UPS)
Supplies (UPS)
HP will be reselling high-end (10 kW and above) three-phase UPS systems from our partners. We will test
and qualify a three-phase UPS for Superdome. The UPS is planned to be available Q1 FY01.
All third-party UPS resold by HP will be tested and qualified by HP to ensure interoperability with
our systems
We plan to include
ups_mond
UPS communications capability in the third-party UPS(s), thus
ensuring consistent communications strategy with our PowerTrust UPS(s)
We will also establish a support strategy with our third party UPS partners to ensure the
appropriate level of support our customer have come to expect from HP.
For more information on the product and to manage the reference sales process. Please go to
http://hpcp.grenoble.hp.com/
for more information.
QuickSpecs
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
8800 and PA-8900)
8800 and PA-8900)
8800 and PA-8900)
8800 and PA-8900)
System Management Features
DA - 11721 Worldwide — Version 28 — October 23, 2009
Page 33