HP Tower UPS

User Guide

Abstract

This document is for the person who installs and maintains HP UPS products. HP assumes you are qualified 

in the installation of electrical equipment and trained in recognizing hazards in products with hazardous 

energy levels.

Part Number: 792523-001
November 17, 2014
Edition: 1

Summary of Contents for Pavilion G4T-1000

Page 1: ...r the person who installs and maintains HP UPS products HP assumes you are qualified in the installation of electrical equipment and trained in recognizing hazards in products with hazardous energy levels Part Number 792523 001 November 17 2014 Edition 1 ...

Page 2: ...pment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries The Tower UPS models that are covered in this manual are intended for installation in an environment within 0 to...

Page 3: ...nd operation described in the manual must be followed in the indicated order A protection circuit breaker must be installed upstream and be easily accessible The system can be disconnected from the AC power source by opening this circuit breaker Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be co...

Page 4: ...munication ports 11 3 4 Ground connection 11 4 Operation 12 4 1 Start up and normal operation 12 4 2 Starting the UPS on battery 12 4 3 UPS shutdown 12 4 4 Operation on battery power 12 4 5 Return of AC input power 12 5 Maintenance 13 5 1 Troubleshooting 13 5 2 Updating the UPS firmware 13 5 3 Battery module replacement 13 5 4 Spares 15 6 Technical Specifications 16 6 1 HP T750 G4 NA JP UPS HP T10...

Page 5: ...yethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations for the disposal of packing materials End of life HP processes products at the end of their service lives in compliance with local regulations HP works with companies in charge of collecting and eliminating our...

Page 6: ...UPS 10 4 kg 23 lb 345 x 150 x 231 mm 13 6 x 5 9 x 9 1 in HP T1500 G4 INTL UPS 15 2 kg 33 5 lb 445 x 150 x 231 mm 17 5 x 5 9 x 9 1 in 1 3 Rear panels HP T750 G4 NA JP UPS HP T1000 G4 NA JP UPS INPUT OUTPUT OUTPUT RS232 OR 5 3 4 1 2 Refer to the Bottom of the unit for caution markings HP T1500 G4 NA JP UPS INPUT OUTPUT RS232 OR Refer to the Bottom of the unit for caution markings 5 3 4 1 2 1 USB com...

Page 7: ... OR 5 4 3 2 1 INPUT OUTPUT OUTPUT Refer to the Bottom of the unit for caution markings RS232 OR 5 4 3 2 1 HP T1500 G4 INTL UPS INPUT OUTPUT Refer to the Bottom of the unit for caution markings RS232 OR 5 4 3 2 1 1 USB communication port 2 RS 232 communication port 3 Outlets for connection of critical equipment 4 Socket for connection to AC power source 5 Ground screw ...

Page 8: ...croll 8 Mute alarm 2 2 LCD window The LCD window provides useful information about the UPS load status events measurements and settings 16 15 14 17 11 10 9 12 13 9 UPS on line mode 10 AVR Automatic Voltage Regulation mode 11 Battery mode 12 Internal fault 13 Output load level 14 Battery level 15 Input measurements 16 Output measurements 17 Measuring unit ...

Page 9: ...HP T1000 G4 INTL UPS HP T1500 G4 INTL UPS Release the scroll down button to select a menu 5s 2s 2s 2s Output voltage Alarm Sensitivity 1 Note In Lo low sensitivity mode the UPS will tolerate more fluctuations in power and goes on battery power less often If the connected load is sensitive to power disturbances keep the sensitivity as Std Standard Example of setting Save the new value 10s 5s 5s Not...

Page 10: ...s are printed on the packing materials to facilitate sorting 1 2 4 5 6 3 2 Battery module connection This operation must be performed when the UPS is switched off and unplugged from the AC source In addition do not disconnect the connector while the unit is operating from the AC source or in reserve mode Note Before starting the UPS connect the internal battery A small amount of arcing may occur w...

Page 11: ...communication ports cannot operate simultaneously 2 1 5 6 A Connect the RS 232 5 or USB 6 communication cable to the serial or USB port on the computer equipment Connect the other end of the communication cable to the USB 1 or RS 232 2 communication port on the UPS The UPS can now communicate with HP power management software 3 4 Ground connection B ...

Page 12: ...ctive alarms before continuing See 5 1 Troubleshooting page 13 4 3 UPS shutdown To shut down the UPS 1 Press the button on the UPS control panel for three seconds 2 The audio alarm beeps and shows a status of UPS shutting OFF The UPS then transfers to Standby mode and the indicator turns off 3 The audio alarm stops 4 4 Operation on battery power Transfer to battery power The connected devices cont...

Page 13: ... is blocking the fan If the error persists note the alarm message and the UPS serial number and then contact your service representative Charger fault The UPS has a charger fault The UPS does not charge the battery anymore Note the alarm message and the UPS serial number and then contact your service representative 5 2 Updating the UPS firmware To update the UPS firmware see the HP website http ww...

Page 14: ...mperatures higher than 60 C 140 F Battery care and storage guidelines Caution Because of the short shelf life of the batteries avoid storing a battery spare as a backup Do not maintain an inventory of spare batteries on site unless a procedure to keep these batteries charged while in storage is implemented To maintain the batteries Minimize the amount of time the UPS uses battery power by matching...

Page 15: ... http www hp com buy parts To replace parts under warranty contact an HP authorized service representative UPS spare parts list Item Spare Part Number SPS UPS T750 G4 NA JP 796774 001 SPS UPS T750 G4 INTL 796775 001 SPS UPS T1000 G4 NA JP 796763 001 SPS UPS T1000 G4 INTL 796771 001 SPS UPS T1500 G4 NA JP 796772 001 SPS UPS T1500 G4 INTL 796773 001 SPS BATTERY KIT UPS T750 765781 001 SPS BATTERY KI...

Page 16: ... Hz 50 Hz system 55 to 65 Hz 60 Hz system Output on battery power Voltage 100 110 120V 10 to 5 1 Frequency 50 60 Hz 0 1 Hz Battery sealed lead acid maintenance free Standard 2 x 12V 7 Ah 2 x 12V 9 Ah 3 x 12V 9 Ah Environment Operating tempera ture range 0 to 35 C 32 to 95 F Storage temperature range 15 to 40 C 5 to 104 F Relative humidity 0 to 90 without condensation Noise level 40 dBA in normal m...

Page 17: ...50 60 Hz 0 1 Hz Battery sealed lead acid maintenance free Standard 1 x 12V 9 Ah 2 x 12V 7 Ah 3 x 12V 9 Ah Environment Operating temperature range 0 to 35 C 32 to 95 F Storage temperature range 15 to 40 C 5 to 104 F Relative humidity 0 to 90 without condensation Noise level 40 dBA in normal mode 1 Adjustable to 220 230 240V but must be set to the identical AC power source value When the UPS is used...

Page 18: ...ial number Product model name and number Product identification number Applicable error messages Add on boards or hardware Third party hardware or software Operating system type and revision level HP contact information For United States and worldwide contact information see the Contact HP website http www hp com go assistance In the United States To contact HP by phone call 1 800 334 5144 For con...