Periodic maintenance 67
Component to be inspected
Task
Frequency
Capable Party
—
Inspect the door operation and
inspect the door gaskets for water
and air leaks.
Annually
Qualified personnel
—
Visually inspect the paint. Perform
prep and touch-up as necessary.
Annually
Qualified personnel
Life safety
Component to be inspected
Task
Frequency
Capable Party
Manual EPO shunt trip
EPO FUNCTIONAL TEST
Manually initiate EPO with the
internal and external push buttons
(if installed) in succession. (Verify
all shunt-trips on all panels trip.)
Annually
Qualified personnel
Thermal EPO shunt trip
EPO FUNCTIONAL TEST
Initiate a thermal (automatic) EPO
shutdown via the EPO
temperature switches located in
the hot aisle. (Verify all shunt-trips
on all panels trip.)
Annually
Qualified personnel
EPO System Test
EPO NON-FUNCTIONAL TEST
Mode Key Switch Test - rotate
keyed switch through all modes.
ARMED MODE - Verify:
•
Power Indicator - White
•
Armed Light - White
BYPASS MODE - Verify
•
Bypass Light - Green
TEST MODE - Verify:
•
Test Light - Amber
Press EPO button (each in
succession) and thermal trip to
verify:
•
Reset Light - White
•
Audible alarm
•
Visual lamp indicator
Replace light upon failure
Annually
Qualified personnel
Emergency Lighting
Verify emergency lighting is
visible when all lighting is off and
the POD doors are shut.
Every 2 years
Qualified personnel
Exit signs
Visually inspect Tritium exit signs
for operation or damage.
Replace as necessary.
Every 2 years
Qualified personnel
Emergency egress
Personnel door emergency egress
panic bars. (Visual and
operational inspection.)
Bi-annually
Qualified personnel