Appendix A
A-5
HP-UX UPS Monitor Error Messages
Timer Controlled Power On/Off Messages
Timer Controlled Power On/Off Messages
The following messages relate to the
Timer Controlled Power On/Off
utility. See
power_onoff(1M)
for more information about the utility.
MESSAGE
ups_mond: Timer Controlled On/Off information invalid;
ignored
SEVERITY
Error. Request to turn off the system (with a later turn on) is ignored.
MEANING
The
power_onoff
utility sent an invalid turn-on time to
ups_mond
.
CAUSE
Internal error in
power_onoff
.
ACTION
Ensure that the requested turn-on date and time are valid, and within range
of the PowerTrust unit's capability.
MESSAGE
ups_mond: mknod error: <error number> for Timed On/Off fifo
file /timed_off; continuing without
SEVERITY
Error.
MEANING
Could not create fifo (also known as a "pipe") for communication between
power_onoff
and
ups_mond
.
CAUSE
File system problem.
ACTION
Refer to
mkfifo(3C)
for more information on the error.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...