Chapter 1
1-25
Overview
Specifications
Overfrequency to Normal:
For 50 Hz operation
below 53.0 Hz
For 60 Hz operation
below 63.0 Hz
AC Output:
Output Voltage (and tolerance):
On-line
230 VAC (+6%/-13%)
On-battery
230 VAC (
±
3%)
Auto or Service Bypass
Same as the AC line input
Output Frequency (and tolerance):
On line
Tracks input frequency
3
On battery
50
±
3 Hz or 60
±
3 Hz
4
Auto or Service Bypass
Same as the AC line input
Rated Output volt-amperes (VA):
On-line
5
5500 VA, continuous
On battery
5
5500 VA, until fully discharged
Auto or Service Bypass
6
5500 VA, continuous
Rated Power:
On Line
7
5500 W, continuous
On battery
7
5500 W, until fully discharged
Auto or Service Bypass
6
5500 VA, continuous
Output Waveshape:
On line
Matches the input waveshape
On battery
Sine wave (with
≤
5% THD)
8
Auto or Service Bypass
Matches the input waveshape
Description
Specification
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...