1-26
Chapter 1
Overview
Specifications
Overload Protection:
On-line or On-battery:
Firmware protection:
For >110% load
Shuts down after a delay
9
Input Breaker protection:
Main UPS circuit breaker (50A)
Auto or Service Bypass:
Bypass circuit breaker (40A)
Output Overload Protection:
At Output #1
Output circuit breaker #1 (16A)
At Output #2
Output circuit breaker #2 (16A)
At Output #3
Output circuit breaker #3 (16A)
At Output #4
Output circuit breaker #4 (Two versions
available, 30A or 40A)
Battery
Type
Maintenance-free sealed lead acid
Nominal voltage
48 VDC
Runtime (@ +25
°
C or above)
15 min. over battery lifetime
Runtime (new battery)
15 min. (+5
°
C to +40
°
C; at 0-3000 m)
Charging Time (@ +25
°
C)
≤
14.5 hours
Lifetime
Approximately 4 years
Environmental Specifications
Operating Limits:
Temperature
10
5
°
to 40
°
C
10
—up to maximum operating altitude
Recommended Temperature
10
20
°
to 25
°
C
10
Humidity
15% to 80% Relative Humidity, non-condensing
at 40
°
C
Altitude
0 to 3,000 meters (10,000 feet)
Non-Operating Limits:
−
40
°
C to 70
°
C
−
15
°
C to 25
°
C for maximum
battery life
Relative Humidity (noncondensing)
5% to 90% at 65
°
C
Altitude
0 - 4572 m (15,000 feet)
Description
Specification
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...