For more information about Telco rack solutions, refer to the
•
.
If you must remove a server from a rack or a non-hot-plug component from a server, power down the
server.
•
Remove the server from the rack
If the rack environment, cabling configuration, or the server location in the rack creates awkward
conditions, remove the server from the rack.
Powering down the server
Before powering down the server for any upgrade or maintenance procedures, perform a backup of critical
server data and programs.
IMPORTANT:
When the server is in standby mode, auxiliary power is still being provided to the system.
To power down the server, use one of the following methods:
• Press and release the Power On/Standby button.
This method initiates a controlled shutdown of applications and the OS before the server enters standby
mode.
• Press and hold the Power On/Standby button for more than 4 seconds to force the server to enter standby
mode.
This method forces the server to enter standby mode without properly exiting applications and the OS. If
an application stops responding, you can use this method to force a shutdown.
• Use a virtual power button selection through iLO.
This method initiates a controlled remote shutdown of applications and the OS before the server enters
standby mode.
Before proceeding, verify that the server is in standby mode by observing that the system power LED is
amber.
Extend the server from the rack
NOTE:
If the optional cable management arm option is installed, you can extend the server without powering
down the server or disconnecting peripheral cables and power cords. These steps are only necessary
with the standard cable management solution.
Procedure
1.
Power down the server (
on page 33).
2.
Disconnect all peripheral cables and power cords.
3.
Loosen the front panel thumbscrews.
4.
Extend the server on the rack rails until the server rail-release latches engage.
WARNING:
To reduce the risk of personal injury or equipment damage, be sure that the rack is adequately
stabilized before extending a component from the rack.
Powering down the server
33
Summary of Contents for ProLiant DL360 Gen10
Page 27: ...Customer self repair 27 ...
Page 28: ...28 Customer self repair ...
Page 29: ...Customer self repair 29 ...
Page 30: ...30 Customer self repair ...
Page 35: ...Removing and replacing the bezel Removing and replacing the bezel 35 ...
Page 66: ...6 Remove the component SFF LFF 66 Removal and replacement procedures ...