HP ProLiant DL560 Server User Guide
Environmental Specifications
Temperature range
Operating
10
°
C to 35
°
C (50
°
F to 95
°
F)
Shipping
-40
°
C to 70
°
C (-40
°
F to 158
°
F)
Maximum wet bulb
temperature
28
°
C (82.4
°
F)
NOTE:
All temperature ratings shown are for sea level. An
altitude derating of 1
°
C per 300 m (1.8
°
F per 1,000 ft to
10,000 ft) is applicable. No direct sunlight allowed.
Relative humidity (noncondensing)
Operating
10% to 90%
Non-operating
5% to 95%
NOTE:
Storage maximum humidity of 95% is based on a
maximum temperature of 45
°
C (113
°
F). Altitude maximum for
storage corresponds to a pressure minimum of 70 KPa.