ENGLISH
Page 29
792519-001 Edition 1
ENGLISH
6. Technical Specifications
6.1 HP R/T2200 G4 NA/JP UPS and HP R/T3000 G4 LV NA/JP UPS
HP R/T2200 G4 NA/JP UPS
HP R/T3000 G4 LV NA/JP UPS
Output Power @ 120V
NA: 1920 VA
1920W
NA: 2880 VA
2700W
Output Power @ 100V
JP: 1500 VA
1400W
JP: 2400 VA
2250W
AC Input power
l
Rated input voltage
l
Input voltage range
l
input frequency range
Single phase 100-125V
80 to 162V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
l
Voltage
l
Frequency
100/120V (-10% to +5%)
(3)
50/60 Hz ±0.1 Hz
Battery
(sealed lead acid,
maintenance free)
l
Standard
l
Additional
modules possible
(up to 4 ERMs)
4 x 12V
9 Ah
6 x 12V
9 Ah
HP R/T2200 G4 ERM
8 x 12V
9 Ah
(2 strings of x4)
HP R/T3000 G4 ERM
12 x 12V
9 Ah
(2 strings of x6)
Environment
l
Operating
temperature range
l
Storage
temperature range
l
Relative humidity
l
Noise level
0 to 40°C
-15 to +50°C
20 to 90% (without condensation)
< 45 dBA
< 50 dBA
(1) The high and low thresholds can be adjusted using UPS settings.
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 120V, but must be set to the identical AC power source value.
Caution:
To reduce the risk of fire, only connect to a circuit provided with 20A maximum branch circuit overcurrent pro-
tection in accordance with the National Electric Code, ANSI/NFPA 70.
Filter
Transformer
AVR
Charger
Inverter
Battery