6.2 HP R/T3000 G4 HV NA/JP UPS and HP R/T3000 G4 INTL UPS
HP R/T3000 G4 HV NA/JP UPS
HP R/T3000 G4 INTL UPS
Output Power @ 200V
2490V
2241W
2490V
2241W
Output Power @ 208V
NA: 3000 VA
2700W
JP: 2490 VA
2241W
—
Output Power @ 230V
—
3000 VA
2700W
AC Input power
l
Rated input voltage
l
Input voltage range
l
input frequency range
Single phase 200-240V
160 to 294V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
l
Voltage
l
Frequency
208/230V (-10% to +5%)
(3)
50/60 Hz ±0.1 Hz
Battery
(sealed lead acid,
maintenance free)
l
Standard
l
Additional
modules possible
(up to 4 ERMs)
6 x 12V
9 Ah
HP R/T3000 G4 ERM
12 x 12V
9 Ah
(2 strings of x6)
Environment
l
Operating
temperature range
l
Storage
temperature range
l
Relative humidity
l
Noise level
0 to 40°C
-15 to +50°C
20 to 90% (without condensation)
< 45 dBA
< 50 dBA
(1) The high and low thresholds can be adjusted using UPS settings (up to 150-294V).
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240V, but must be set to the identical AC power source value.
When the UPS is used in the EU area, use an external circuit breaker in front of the line with rating 16A,
250V which is IEC/EN 60898-1 standard compliant.
When the UPS is used in the NA area, use an external circuit breaker in front of the line with rating 20A, 250V.
Caution:
To reduce the risk of fire, only connect to a circuit provided with 30A maximum branch circuit overcurrent pro-
tection in accordance with the National Electric Code, ANSI/NFPA 70.
6. Technical Specifications
Filter
Transformer
AVR
Charger
Inverter
Battery