Remote Emergency Power Off
The UPS includes a Remote Emergency Power Off (REPO) port. When properly wired, the
REPO port allows the power at the UPS output receptacles to be switched off from a remote
location. Local or national wiring regulations may require REPO capabilities.
WARNING: To prevent personal injury or damage to equipment, take the following
precautions:
•
The REPO port must be wired by a qualified electrician.
•
The main breaker switch must be in the off position before wiring the REPO port.
•
Remote circuits connected to the REPO port must comply with local building
wiring codes and methods. In North America, the NEC (NFPA 70, Article 725) is a
minimum requirement.