Specifications 112
Specifications
Environmental specifications
Feature
Specification
Operating temperature 10°C-35°C (50°F-95°F); UL-tested at 30°C (86°F)
Non-operating
temperature
-25°C-60°C (-13°F-140°F)
Relative humidity
5%-95%; non-condensing
Operating altitude
Up to 3050 m (10,000 ft) above sea level
Non-operating altitude
9144 m (30,000 ft) above sea level
Audible noise
</= 55 dBA
Power unit physical specifications
1U R12000DF specifications
Parameter
Value
Height
4.25 cm (1.7 in)
Depth
67.7 cm (26.7 in)
Total depth
67.7 cm (26.7 in)
Width
48.26 cm (19.0 in)
Weight
16 kg (35.2 lb)
Ambient operation
10°C-35°C (50°F-95°F)
2U R18000DF specifications
Parameter
Value
Height
8.6 cm (3.386 in)
Depth
67.7 cm (26.654 in)
Total depth
92.2 cm (36.299 in)
Width
48.26 cm (19.000 in)
Weight
20.87 kg (46 lb)
REPO port specifications
The REPO port meets the requirements of NFPA Articles 645-10 and 645-11 for a Disconnecting Means.
Battery pack physical specifications
The following tables include specifications for the DirectFlow Battery Packs and battery modules.
Summary of Contents for R12000 XR
Page 17: ...Overview 17 o Two 3U DirectFlow Battery Packs o Two 1U DirectFlow Battery Packs ...
Page 98: ...Troubleshooting 98 ...
Page 99: ...Troubleshooting 99 ...
Page 100: ...Troubleshooting 100 ...
Page 101: ...Troubleshooting 101 ...
Page 102: ...Troubleshooting 102 ...
Page 103: ...Troubleshooting 103 ...
Page 104: ...Troubleshooting 104 ...
Page 105: ...Troubleshooting 105 ...
Page 106: ...Troubleshooting 106 ...
Page 107: ...Troubleshooting 107 ...
Page 108: ...Troubleshooting 108 ...
Page 109: ...Troubleshooting 109 ...
Page 110: ...Troubleshooting 110 ...
Page 111: ...Troubleshooting 111 ...