Position 

 

 

WARNING:  To prevent personal injury or damage to the 
equipment, take the following precautions when installing the 
equipment: 

• 

The UPS must be installed at the bottom of the rack. If 
placed in the rack with existing equipment, the rack must be 
reconfigured to allow installation of the UPS at the bottom of 
the rack. 

• 

The UPS must be mounted on the rails included in the UPS 
kit. Use the rack template tool included in the kit to align the 
rails. 

Checking the Battery  
Recharge Date 

Before unpacking the UPS, check the battery recharge date 
specified on the battery recharge date label that is affixed to the 
shipping carton. 

 

IMPORTANT:

  Do not use the battery if the recharge date has passed. If the 

date on the battery recharge date label has passed without the battery being 
recharged, contact an HP authorized service representative for directions. 

 

NOTE:

  The following label is only an example date. The date on your carton 

may be different. 

 

THIS PRODUCT CONTAINS
A NONSPILLABLE BATTERY

Next Recharge Date:

Please refer to Maintenance Section

of Owner's Manual enclosed inside

14-DEC-04

 

Kit Contents 

Documentation 

• 

International Regulatory Compliance

 guide 

• 

Important Safety Information

 guide 

• 

Power Products Documentation CD 

• 

Rack and Power Management Pack CD 

• 

This document 

Rails 

• 

Rails, with mounting hardware 

• 

Rack template tool 2U (295523-023) 

UPS 

• 

UPS chassis 

• 

Front bezel 

• 

Rear stabilization brackets (2) 

• 

Remote Emergency Power Off (REPO) port and  
connector block 

• 

Battery pack (1) 

Additional Hardware 

The following items are supplied for shipping a rack with a  
UPS installed: 

• 

M6 nuts (4) 

• 

M6 flat washers (4) 

• 

M6 split washers (4) 

Cables

 

• 

The R1500 XR NA model ships with a non-detachable input 
power cord with a NEMA 5-15 plug and a 3.66-meter (12-foot) 
UPS/computer interface cable (201092-002). 

• 

The R1500 XR JPN model ships with a non-detachable input 
power cord with a NEMA 5-20 plug and a 3.66-meter (12-foot) 
UPS/computer interface cable (201092-002). 

• 

The R1500 XR H INT’L model ships with: 

 

Two 10 A, 2.44-meter (8-foot) IEC-to-IEC power cords 
(142263-002) 

 

Two 10 A, 3.05-meter (10-foot) IEC-to-IEC power cords 
(142263-003), for load equipment power 

 

A 3.66-meter (12-foot) UPS/computer interface cable 
(201092-002) 

Use the jumper cord supplied with the UPS to attach your 
equipment to the output of the UPS. Use the equipment power cord 
to attach the UPS to utility power using the IEC-320-C14 inlet on 
the rear of the unit. 

 

NOTE:

  All models ship with a computer interface cable. The computer 

interface cable is not needed for normal operation. To administer the UPS 
with power management software, connect the interface cable between the 
UPS communications port and the serial port on the host computer. 

Tools and Materials Required 

The following tools are required: 

• 

#2 Phillips screwdriver

 

The following items are supplied with the rack: 

• 

Screws

 

• 

Cage nuts

 

• 

Cage nut-fitting tool 

Summary of Contents for R1500 XR SERIES

Page 1: ...onductor leakage current Do not operate a UPS that is disconnected from the utility power source Disconnect protected devices from the UPS before disconnecting the UPS from utility power Use the Test Alarm Reset button to test the batteries rather than unplugging the UPS Refer to the UPS user guide for more information on the operation of the UPS Regulatory Compliance Identification Numbers For re...

Page 2: ...te tool 2U 295523 023 UPS UPS chassis Front bezel Rear stabilization brackets 2 Remote Emergency Power Off REPO port and connector block Battery pack 1 Additional Hardware The following items are supplied for shipping a rack with a UPS installed M6 nuts 4 M6 flat washers 4 M6 split washers 4 Cables The R1500 XR NA model ships with a non detachable input power cord with a NEMA 5 15 plug and a 3 66 ...

Page 3: ...near the rack where it will be assembled Follow the unpacking instructions on the carton Mounting the Rails The UPS must be mounted on the fixed rails supplied with the UPS Before beginning this installation process review and adhere to the following precautions WARNING To prevent personal injury verify that the rack containing the UPS is stable The following conditions must be met The leveling fe...

Page 4: ...lift out tray 4 With one person on each side lift the chassis to rail level and slide it into place on the mounting rail 5 Attach the chassis to the rack using the screws and the cage nuts supplied with the rack NOTE After installing the UPS chassis insert additional screws for support if any screw holes are unoccupied Completing the UPS Assembly Connecting the Communications Port The UPS includes...

Page 5: ...m a remote location To activate the REPO port 1 Install a suitable switch at the required remote location 2 Remove the connector block from the REPO port 3 Wire the connector block using stranded non shielded wire AWG 22 18 or equivalent 4 Replace the connector block in the REPO port IMPORTANT The REPO port must meet the requirements of the NFPA Articles 645 10 and 645 11 for a disconnecting means...

Page 6: ... NOTE The Configure Mode On LED the Configure button and the voltage configuration panel are accessible only when the front bezel is removed Utility LED 5 Flashing Red Utility input voltage is outside the 20 to 30 configured nominal range Green Utility voltage is present and output is on or utility voltage has returned to the voltage range that was configured UPS is supplying utility power and aud...

Page 7: ... Press the Standby button to take the UPS out of Operate mode Power to the load receptacles ceases 3 Disconnect the UPS from utility power 4 Wait at least 60 seconds while the UPS internal circuitry discharges For more information refer to the HP website at www hp com products ups ...